beautypg.com

Programming chapter 3 – Rockwell Automation 1771-PD PID MODULE (+DU) User Manual

Page 128

background image

Programming

Chapter 3

3Ć85

Figure 3.29

Cascade Control

Process

PID

SP1

E

PV1

BIAS1

V

11134

PID

BIAS2

E

SP2

PV2

PV1 is the input to the primary, outer, or master loop.

PV2 is the input to the secondary, inner, or slave loop.

Feedforward Control

Feedforward control is shown in Figure 3.30. A disturbance is fed
forward to the PID module to change the output before the disturbance
changes the process variable. The PID module can perform one or more
of the following functions on the feedforward input: square root, lead/lag,
multiplication by a gain constant, and add an offset. Feedforward is often
used to control processes with transportation lag.

Figure 3.30

Feedforward Control

Process

PID

SP

E

PV

BIAS

V

11135

FF

FF represents the Feedforward Control algorithm

Disturbance