Network status led (net led), Rs-232 port led indicator, Fault conditions – Rockwell Automation 1761-NET-DNI DeviceNet Interface (DNI) User Manual
Page 64
Publication 1761-UM005B-EN-P - October 2006
64 Setup, Programming, and Troubleshooting
Network Status LED (NET LED)
The network status LED provides information specific to the
DeviceNet network.
RS-232 Port LED Indicator
The DNI has a green LED next to the RS-232 connector to provide
communications activity status. The LED is lit whenever data is being
transmitted or received. When communications are occurring, this
LED will appear to be flashing.
Fault Conditions
The following table defines causes of faults in the DNI.
Network Status LED
LED Condition
DNI State
Problem/Indication
Off
Not Powered/Not
On-Line
DNI is not on-line.
• DNI has not completed the
Dup_MAC_ID test yet.
• DNI may not be powered.
Flashing Green
(1)
(1)
Normal condition.
On-Line, Not
Connected
DNI has passed the Dup_MAC_ID test, is
on-line, but has not established connections
to other nodes.
Green
(1)
On-Line, Connected The DNI has one or more valid established
connections. This can be either I/O or
Messaging
Flashing Red
Connection
Time-Out
I/O connection(s) are in the timed-out state.
Red
Critical Link Failure Failed communication device. The DNI has
detected an error that has rendered it
incapable of communicating on the network
(Bus-Off error). If the error is Duplicate MAC
ID, the DNI only communicates via the Group
4 off-line connection set.
Flashing Red-Green
Communication
Faulted
A specific communication fault recovery
stage or self-test.
Fault Conditions
MOD LED
NET LED
Fault Condition
DeviceNet Standard Fault
Available Recovery Options
Solid Red
Not Applicable
Self-Test Failure
Module - Major Unrecoverable Fault Power Cycle
Flash Red
Not Applicable
Invalid Configuration
Parameter
Module - Minor Recoverable Fault
Modify Invalid Parameter
Flash Red
Not Applicable
EEPROM Invalid
Module - Major Recoverable Fault
Re-commission the DNI.
Not Applicable Solid Red
Duplicate Node Detected
Communication Fault
Power Cycle, Group 4 Fault Recovery
Not Applicable Solid Red
Bus-Off Error
Communication Fault
Power Cycle, set bus-off attribute of
DeviceNet object to 1.