beautypg.com

Input type, Input data file – Rockwell Automation 1761-NET-DNI DeviceNet Interface (DNI) User Manual

Page 33

background image

Publication 1761-UM005B-EN-P - October 2006

DNI Configuration Parameters and Programming Notes 33

Input Type

This parameter is used to identify the type of data to be read within
the controller. The DNI supports data exchange with either bit or
integer files.

Input Data File

This parameter is used to identify the data file to be read within the
controller. The following table shows the files within Allen-Bradley
controllers.

Parameter
Type

Parameter Number

Description

Range

Default
Value

Series A

Series B

I/O

5

3

Input Type

Bit or Integer File

Integer File

Parameter
Type

Parameter Number

Description

Range

Default Value

Series A

Series B

I/O

6

4

Input Data File

3…254

7

Controller

Input Data Files

Number Values

MicroLogix 1000

Bit

3

Integer

7

SLC/Other MicroLogix

Bit

3, 10-255

Integer

7, 9-255

PLC

Bit

3, 10-999

Integer

7, 9-999

TIP

The DNI can access only files 3…254.