beautypg.com

Rockwell Automation 1761-NET-DNI DeviceNet Interface (DNI) User Manual

Page 40

background image

Publication 1761-UM005B-EN-P - October 2006

40 DNI Configuration Parameters and Programming Notes

The sizes of compatible data files within Allen-Bradley controllers vary
based on the DFI device selected.

Controller Data Files

Controller

Output Data Files

File Sizes

MicroLogix 1000

Bit

32 Words

Integer

105 Words

SLC/Other MicroLogix

Bit

255 Words

Integer

255 Words

PLC

Bit

999 Words

Integer

999 Words

TIP

The DNI can only access files 0…254.

IMPORTANT

You must have sufficient room in the file that you
select. Make sure the Output Word Offset plus the
Output Size does not exceed the boundary of the
data file. For example, a MicroLogix 1000 controller
has 32 words in its bit file; therefore, you could not
use a Output Word Offset of 30 and a Output Size of
5 because this exceeds the file size.

IMPORTANT

If you use RSNetWorx or DeviceNet Manager to
configure/commission the DNI, it is up to the user to
select the correct values for:

• Output Size
• Output Split Point (DNI Series B only)
• Output Type
• Output Data File
• Output Word Offset

Only the DNI Configuration Software Utility
performs checks on the information entered.