beautypg.com

Input size – Rockwell Automation 1761-NET-DNI DeviceNet Interface (DNI) User Manual

Page 29

background image

Publication 1761-UM005B-EN-P - October 2006

DNI Configuration Parameters and Programming Notes 29

Input Size

This parameter identifies the size, in words, of the data array that is
read from the controller attached to the DNI’s RS-232 port.

The array may contain up to 16 (16-bit) words of data for DNI Series A
(32 words for DNI Series B) from a contiguous block within the
attached controller.

Messaging

2

15

Message Timeout

0…2500 ms

0 ms

46

Messaging

Not
Applicable

16

DF1 Substitute
Address

0…64

64 = Disabled

47

DF1

15

17

DF1 Autobaud

Disabled (0) or
Enabled (1)

Enabled (1)

47

DF1

16

18

DF1 Baud Rate

0…5:
0: 38,400
1: 19,200
2: 9600
3: 4800
4: 2400
5: 1200

Series A: 2 = 9600
Series B: 1 = 19,200

48

DeviceNet

1

19

DeviceNet Autobaud Disabled (0) or

Enabled (1)

Enabled (1)

48

Device

17

Not
Applicable

DNI Mode

Standby (0) or
Operational (1)

Operational (1)

49

EDS Parameters for the DNI

Input Size Parameter Definition

Parameter
Type

Parameter Number Description

Range

Default
Value

Series
A

Series B

I/O

4

1

Input Size

Series A: 1…16
Series B: 1…32

1

IMPORTANT

For DNI Series B, you must also configure the Input
Split Point.

See Input Split Point on page 30.