Publication 1761-UM005B-EN-P - October 2006

28 DNI Configuration Parameters and Programming Notes

EDS Parameters for the DNI

The following list shows the available parameters for configuring the
DNI. Parameter definitions and usage information are provided in the
sections following the table.

IMPORTANT

When modifying most DNI parameters, you must
first disable polling (Set the Data Enable parameter
to disable for DNI Series A. Set the I/O Scan Enable
parameter to disable for DNI Series B). You can
enable polling after setting your configuration.

For information on how to set up and modify
parameters, see Setup, Programming, and
Troubleshooting on page 53
.

EDS Parameters for the DNI

Parameter
Type

Parameter Number

Description

Range

Default Value

For More
Information

Series A

Series B

I/O

4

1

Input Size

Series A: 1…16
Series B: 1…32

1 word

29

I/O

Not
Applicable

2

Input Split Point

1…32

1 word

30

I/O

5

3

Input Type

Bit or Integer File

Integer File

33

I/O

6

4

Input Data File

3…254

7

33

I/O

7

5

Input Word Offset

0…254

0

34

I/O

8

6

Output Size

Series A: 1…16
Series B: 1…32

1 word

35

I/O

Not
Applicable

7

Output Split Point

1…32

1 word

36

I/O

9

8

Output Type

Bit or Integer File

Integer File

38

I/O

10

9

Output Data File

3…254

7

39

I/O

11

10

Output Word Offset

0…254

1

39

I/O

14

11

DF1 Device

0…3:
0: Other
1: PLC
2: SLC/ Other
MicroLogix
3: MicroLogix 1000

3 = MicroLogix 1000

41

I/O

3

12

DNI Series A: Data
Enable
DNI Series B: I/O
Scan Enable
(Polling Enable)

Disabled (0) or
Enabled (1)

Disabled (0)

41

I/O

12

13

DF1 Heartbeat

Series A: 2…10
Series B: 1…10

2

43

I/O

13

14

Data Scan Delay
(Polling Delay)

20…3000 ms

50 ms

45