Eds parameters for the dni – Rockwell Automation 1761-NET-DNI DeviceNet Interface (DNI) User Manual
Page 28
Publication 1761-UM005B-EN-P - October 2006
28 DNI Configuration Parameters and Programming Notes
EDS Parameters for the DNI
The following list shows the available parameters for configuring the
DNI. Parameter definitions and usage information are provided in the
sections following the table.
IMPORTANT
When modifying most DNI parameters, you must
first disable polling (Set the Data Enable parameter
to disable for DNI Series A. Set the I/O Scan Enable
parameter to disable for DNI Series B). You can
enable polling after setting your configuration.
For information on how to set up and modify
parameters, see Setup, Programming, and
Troubleshooting on page 53.
EDS Parameters for the DNI
Parameter
Type
Parameter Number
Description
Range
Default Value
For More
Information
Series A
Series B
I/O
4
1
Input Size
Series A: 1…16
Series B: 1…32
1 word
I/O
Not
Applicable
2
Input Split Point
1…32
1 word
I/O
5
3
Input Type
Bit or Integer File
Integer File
I/O
6
4
Input Data File
3…254
7
I/O
7
5
Input Word Offset
0…254
0
I/O
8
6
Output Size
Series A: 1…16
Series B: 1…32
1 word
I/O
Not
Applicable
7
Output Split Point
1…32
1 word
I/O
9
8
Output Type
Bit or Integer File
Integer File
I/O
10
9
Output Data File
3…254
7
I/O
11
10
Output Word Offset
0…254
1
I/O
14
11
DF1 Device
0…3:
0: Other
1: PLC
2: SLC/ Other
MicroLogix
3: MicroLogix 1000
3 = MicroLogix 1000
I/O
3
12
DNI Series A: Data
Enable
DNI Series B: I/O
Scan Enable
(Polling Enable)
Disabled (0) or
Enabled (1)
Disabled (0)
I/O
12
13
DF1 Heartbeat
Series A: 2…10
Series B: 1…10
2
I/O
13
14
Data Scan Delay
(Polling Delay)
20…3000 ms
50 ms