Quick Start 13

Configuring Master/Slave
I/O

Follow these steps to configure a DNI connected to a MicroLogix 1000
controller as a slave device to a DeviceNet master.

1. Unpack and mount the DNI.

2. Connect the DNI to the DeviceNet Network.

When power is first applied to the DNI, it resides at node 63 on
the network. The DNI out-of-box configuration is defaulted to
Autobaud; it synchronizes to the DeviceNet network baud rate.

3. Connect to the DNI with your network configuration tool

(software such as DeviceNet Manager or RSNetWorx) and set the
DNI to the desired node number. This is called node
commissioning.

4. Double-click on the DNI icon to open the DNI’s EDS.

5. For DNI Series A: set DNI Mode (parameter 17) to Standby mode

(0).

For DNI Series B: set I/O Scan Enable (parameter 12) to disable
(0) (default).

6. Click Save to Device.

IMPORTANT

You must have the DNI’s EDS (electronic data sheet) file and
bitmap file (or icon) loaded into your configuration software.
See DNI Software Files on page 53 and Setting Up Network
Configuration Software on page 55
for more information.