beautypg.com

Rockwell Automation Logix5000 Controllers Add-on Instructions Programming Manual User Manual

Page 33

background image

Designing Add-On Instructions

Chapter 1

The following picture shows Simulation instruction in a ladder.

• If you want the parameter’s value displayed on the instruction face in

Ladder, set the parameter as visible.

• An Output parameter of the BOOL tag type that is not required, but

visible, will show as a status flag on the right side of the block in Ladder.

This can be used for status flags like DN or ER.

This table explains the effects of the Required and Visible parameter settings on
the display of the instructions.

Parameter

Type

Is the

Parameter

Required?

Is the

Parameter

Visible?

Ladder Diagram

Function Block Diagram

Structured Text

Does the

Value
display?

Does the

Argument
display?

Do You Need to

Connect the
Parameter?

Does the

Argument
display?

Can You Change the
Visibility Setting

Within the Function
Block?

Does the

Argument
display?

Input

Y

Y

Y

Y

Y

N/A

N

Y

Input

N

Y

Y

N

N

N/A

Y

N

Input

N

N

N

N

N

N/A

Y

N

Output

Y

Y

Y

Y

Y

N/A

N

Y

Output

N

Y

Y

N

N

N/A

Y

N

Output

N

N

N

N

N

/A

Y

N

InOut

Y

Y

N

Y

N/A

Y

N

Y

If you have a parameter for which the user must specify a tag as its source for input

or its destination as output, and you do not want this to be optional, set the
parameter as required. Any required parameters are automatically set to visible.

The Visible setting is always set to visible for InOut parameters. All InOut

parameters are required.

Rock well Automati on Publication 1756- PM010F-EN-P - Oct ober 2014

33