Rockwell Automation 1785-LTx,D17856.2.1 Classic PLC-5 Programmable Controllers Users Manual User Manual
Page 106

Transferring Discrete and BlockĆTransfer Data
Chapter 8
8-11
Supervisory Processor (PLCĆ2/30, PLCĆ3, PLCĆ5, or PLCĆ5/250)
Follow these guidelines when programming block-transfer instructions in
the supervisory processor.
Set the length to 0.
Set the continuous bit for continuous operation (PLC-5 and -5/250
processors only).
Use the remote I/O rack number for which you configure the adapter-
mode processor.
Use 0 for the group and module numbers.
Condition the use of BTR data with a “data valid” bit.
All address comments for contacts shown in the following examples
represent the set (1) state of the bit in the PLC-5 processor.
Figure 8.6
Example Block Transfer in PLCĆ2/30 Supervisory Processor
EN
BLOCK TRANSFER READ
DATA ADDR
MODULE ADDR
BLOCK LENGTH
FILE
031
200
0
240-337
Store Bit
DN
PLCĆ5 adapterĆmode processor in rack 2
EN
BLOCK TRANSFER WRITE
DATA ADDR
MODULE ADDR
BLOCK LENGTH
FILE
030
200
0
140-237
Store Bit
DN
U
BTW Done Bit
07
Store Bit
L
BTR Done Bit
120
Store Bit
FILE TO FILE MOVE
COUNTER ADDRESS
POSITION
033
0
BTR Done Bit
Data Valid Bit
120
06
07
020
120
07
06
020
120
06
120
06
120
10
FILE LENGTH
FILE A:
64
240-337
FILE R:
RATE PER SCAN
400-477
64
BTW
BTR
FFM
SEND DATA TO ADAPTERĆMODE PROCESSOR
READ DATA FROM ADAPTERĆMODE PROCESSOR
BUFFER READ DATA FROM
ADAPTERĆMODE PROC TO WORK
FILE AREA