6 - troubleshoot the switch, Ip address issues, Chapter 6 – Rockwell Automation 1783-Mxxx Stratix 8000 and 8300 Ethernet Managed Switches User Manual User Manual
Page 169: Troubleshoot the switch, Chapter
Rockwell Automation Publication 1783-UM003I-EN-P - March 2014
169
Chapter
6
Troubleshoot the Switch
This chapter helps you resolve issues related to Stratix 8000 and Stratix 8300
switches and perform common functions, such as resetting a switch.
For additional troubleshooting, refer to the following:
•
Diagnose Cabling Problems on page 131
•
View System Log Messages on page 132
IP Address Issues
Following are some basic troubleshooting tips for issues related to the switch IP
address.
Topic
Page
Device Manager Web Interface Issues
Recover the Switch Firmware and Restore Factory Defaults
Troubleshoot a Firmware Upgrade
Table 21 - IP Address Issues
Issue
Resolution
IP address is not received from DHCP server
If the switch does not receive an IP address from an upstream device operating as a DHCP server, make sure that the
upstream device is operating as a DHCP server and again follow the procedures to set up the switch in
Chapter 2, Getting
Switch has wrong IP address
If the switch is installed in your network but you cannot access the switch because it has the wrong IP address, assign a
new switch IP address.
Refer to Access Direct Managed Mode on page 171
to assign the IP address, and then update the
switch IP address on the Device Manager Express Setup window.