Rockwell Automation 1783-Mxxx Stratix 8000 and 8300 Ethernet Managed Switches User Manual User Manual
Page 130
130
Rockwell Automation Publication 1783-UM003I-EN-P - March 2014
Chapter 4 Manage the Switch via the Device Manager Web Interface
To monitor CIP status, from the Monitor menu, choose CIP Status.
Table 16 - CIP Status Fields
Field
Description
Overview
State
The state of the CIP connection (Enabled or Disabled).
Vlan
The VLAN ID.
CIP I/O Connection Owner
The IP address of the device to and from which application-specific I/O output data is sent and received.
CIP Config Session Owner
The IP address of the device controlling the CIP configuration session.
Management CPU Utilization (%)
Percentage of the Management CPU used for management functions. Switch functions have dedicated ASICs that are not impacted by
management functions.
Active Explicit Msg Connections
The number of active, explicit messaging connections to the switch as a target.
Active I/O Connections
The number of active I/O connections with the switch as a target.
Active Multicast Groups
The number of multicast groups, including CIP multicast groups flowing through the switch.
Connection Details
Open Requests
The number of Forward Open requests received by the switch to establish a connection with the switch.
Close Requests
The number of Forward Close requests received by the switch after a connection was successfully established with the switch.
Open Format Rejects
The number of Forward Open requests directed to the switch that failed because the request is not in the proper format.
Close Format Rejects
The number of Forward Close requests directed to the switch that failed because the request is not in the proper format.
Open Resource Rejects
The number of Forward Open requests that failed to establish a new connection for reasons such as insufficient memory.
Close Other Rejects
The number of Forward Close requests that failed for reasons such as incompatible electronic keying.
Open Other Rejects
The number of Forward Open requests that failed for reasons such as incompatible electronic keying.
Connection Timeouts
The number of CIP connections that timed out due to inactivity.