Example Programs
Publication 1771-UM002A–EN–P – May 2000
Position
Number
1
Function
Word
Description
Equivalent
Word
2
055
466
Final Rate
zero (ignored by stepper controller
module).
056
467
Decel Time
1.0 seconds (only used if needed for
controlled stop).
057 - 058
470 - 471
Final Position
19,200 pulses. The position where
the final rate is zero.
059
472
SMCW
C000 hex. This begins the return
move, move 10.
060
473
Ramp Time
2.0 seconds to reach final rate in
reverse
061
474
Final Rate
2000 pulses/second in reverse.
062
475
Decel
3.0 seconds required value in last
move.
063 , 064
476, 477
MS. LS Position
000,000 pulses (starting position).
1
Position number of the data monitor display of FFM 0033.
2
Equivalent words in file A of FFM 0033.
Ladder Diagram 1-Axis Program
An example ladder diagram program for a 1-axis profile is presented
in Figure 4.4. A description of each rung follows:
Rungs 1 and 2
These rungs provide a controlled stop. When bit 110/15 is true, bit
500/06 (moveset control word, stop bit) is true and bit 500/07
(moveset control word, decel/inst bit) is true. The stepper controller
module will perform a controlled stop using the decel value in the
move being processed at the time the stop command is received.
Rung 3
This rung provides a reset (i.e. clears all status and position
information) to re-initialize the stepper controller module. When bit
112/03 is true, bit 500/04 (moveset control word, reset bit) is true.
Therefore, the controller module is rest.
Rung 4
This rung is used to start the positioning profile. When bit 110/14 is
true, bit 500/00 (moveset control word, start bit) is true. Execution
of the positioning profile begins.
Rung 5
This rung provides an initialized preset. When bit 110/16 is true, bit
502/17 (most significant preset word, bit 17) is true. Therefore, a
preset is performed.