Appendix B

Codes

B-4

HART Field Device Error Codes
Integer Word 36

Bit

Error Code

Description

7

Field Device Malfunction

An internal hardware error or failure has been detected by the HART field device.

6

Configuration Changed

A write or set command has been executed on the HART field device.

5

Cold Start

Power has been removed and reapplied resulting in the reinstallation of the setup

information. The first HART command to recognize this condition automatically resets

this flag. This flag may also be set following a master reset or self test.

4

More Status Available

More status information is available and can be read using HART command 48,

Read Additional Status Information.
Note: HART command 48 is not supported by the STT subroutine.

3

Primary Variable Analog Output Fixed

The analog and digital outputs for the primary variable are held at their requested

value. They will not respond to the applied process.

2

Primary Variable Analog Output Saturated

The analog and digital outputs for the primary variables are beyond their limits and no

longer represent the true applied process.

1

NonĆPrimary Variable Out of Limits

The process applied to a sensor, other than that of the Primary Variable, is beyond

the operating limits of the device. To identify the variable, use command #48, Read

Additional Status Information.

0

Primary Variable Out of Limits

The process applied to the sensor for the primary variable is beyond the operating

limits of the device.