Appendix B

Codes

B-2

Smart Transmitter Interface Error Codes
Integer Word 33

General Errors

Code (decimal)

Code (hex)

Definition

Description

0

00

No Error

The Smart Transmitter Interface processed the last received command, and

no errors were detected.

1

01

Downloading Firmware

The Smart Transmitter Interface firmware is being upgraded over the

RSĆ232C port. The last received command cannot be processed.

2

02

No Corresponding BTW

The Smart Transmitter Interface received a BTR but does not know what data

is being requested. All BTRs must be preceded by a BTW indicating what

response to return in a BTR.

3

03

Command Still in

Progress

The Smart Transmitter Interface is still obtaining the HART Response from a

field device and cannot respond with the requested data. The programmable

controller should reissue the BTR request to obtain the response.

Command Errors

Code (decimal)

Code (hex)

Definition

Description

16

10

Invalid Command

The Smart Transmitter Interface command is invalid and cannot be

processed.

17

11

Invalid Channel Number

The Smart Transmitter Interface channel number is invalid. The command

cannot be processed.

18

12

Invalid HART Message

The HART packet encapsulated within a Smart Transmitter Interface packet is

invalid and cannot be forwarded to a field device.

19

13

Invalid Channel List

The channel list provided with the Enable Burst Monitor Mode command

contains an invalid entry or is incorrectly terminated. The command cannot be

processed.

20

14

Invalid Parameter

An invalid parameter is provided with the Smart Transmitter Interface

command and so it cannot be processed.

21

15

Invalid Control

An invalid control byte is included with the Smart transmitter Interface

command. The command cannot be processed.

22

16

Invalid DF1 Packet Length The length of the DF1 packet is not consistent with the length specification in

that packet. The command cannot be processed.

Device Errors

Code (decimal)

Code (hex)

Definition

Description

32

20

Burst Mode Device Not

Communicating

The Smart Transmitter Interface is not receiving burst data from a field device

in burst mode. Either Burst mode has been turned off in the field device or it is

too busy to send burst table data. The error code is cleared once the Smart

Transmitter Interface receives new burst data from the device.

33

21

No Response Received

From Device

The Smart Transmitter Interface has not received a response from a field

device after exhausting all retry attempts.

34

22

No Valid Burst Data

The Smart Transmitter Interface does not have data in its Burst Monitor Table

for the requested channel. Either the Smart Transmitter Interface was not

commanded to monitor the channel for burst data, or the field device is not in

burst mode.