beautypg.com

Ać10, Hart command 38 – Rockwell Automation 1770,D17706.5.21 SMART TRANSMITTER TOOLKI User Manual

Page 45

background image

HART Command Data Table Layouts

Appendix A

A-10

Use this command to reset the configuration change flag.

Standard Inputs

Integer

Word 0

I/O Rack Number of 1770ĆHT1

Word 1

I/O Group Number of 1770ĆHT1

Word 2

Channel Number of HART field device

Word 3

Polling Address of HART field device

Word 4

Smart Transmitter Interface Command Number 16 (decimal)

Word 5

HART Command Number 38

CommandĆspecific Inputs

Integer

Words 6 Ć 8

HART address from HART Command 0

Data Table Report PLC-5/25 Addr 31 Data Table File N10:0

Address 0 1 2 3 4 5 6 7 8 9

N10:0 4 6 3 0 16 38 9858 269 12807 0

N10:10 0 0 0 0 0 0 0 0 0 0

N10:20 0 0 0 0 0 0 0 0 0 0

N10:30 0 0 0 0 0 0 0 0 0 0

N10:40 0 0 0 0 0 0 0 0 0 0

N10:50 0 0 0 0 0 0 0 0 0 0

These six integer words are the

standard inputs that are required for

each HART command (see page 3Ć3).

This is the HART address that is returned

from HART Command 0 (see page AĆ3).

HART Command 38

Reset Configuration Change Flag