background image

HART Command Data Table Layouts

Appendix A

A-7

Standard Outputs

Integer

Word 30

STT Subroutine Status Word

g

Word 31

STT Subroutine Error Code

Word 32

Smart Transmitter Interface Status Word

Word 33

Smart Transmitter Interface Error Code

Word 34

HART ProtocolĆCommunication Error Code

Word 35

HART Command Response Summary Code

Word 36

HART Field Device Error Code

CommandĆspecific Outputs

Integer

Word 41

Primary Variable Unit Code

g

Word 42

Secondary Variable Unit Code

Word 43

Tertiary Variable Unit Code

Word 44

4th Variable Unit Code

FloatingĆpoint

Word 10

Primary Variable Current

g p

Word 11

Primary Variable

Word 12

Secondary Variable

Word 13

Tertiary Variable

Word 14

4th Variable

Data Table Report PLC-5/25 Addr 31 Data Table File N10:0

Address 0 1 2 3 4 5 6 7 8 9

N10:0 4 6 3 0 16 3 9858 269 12807 0

N10:10 0 0 0 0 0 0 0 0 0 0

N10:20 0 0 0 0 0 0 0 0 0 0

N10:30 4 0 128 0 0 0 0 0 0 0

N10:40 0 32 250 250 250 0 0 0 0 0

N10:50 0 0 0 0 0 0 0 0 0 0

These four integer words are the commandĆspecific outputs

that contain the unit codes for the variables (see page BĆ5).

These seven integer words are the standard outputs

that contain the status of the communications with

the HART field device. (see page 3Ć6).

These four floatingĆpoint words are commandĆspecific outputs

that contain the variables from the HART field device.

Data Table Report PLC-5/25 Addr 31 Data Table File F11:0

Address 0 1 2 3 4

F11:0 0 0 0 0 0

F11:5 0 0 0 0 0

F11:10 7.29 20.58 0 0 0

F11:15 0 0 0 0 0

This floatingĆpoint word is a commandĆspecific

output that contains the primary variable current.

HART Command 3

Read Dynamic Variables & Primary

Variable Current