Example 3 (continued) – Rockwell Automation 1770,D17706.5.21 SMART TRANSMITTER TOOLKI User Manual
Page 35
Chapter 3
Using The Smart Tranmsitter Toolkit
3-16
Example 3 (continued)
Rung 2:4
Call the STT subroutine unconditionally.
| STT |
| Subroutine |
| +JSR–––––––––––––––+ |
+–––––––––––––––––––––––––––––––––––––––––––––––––––––––––+JUMP TO SUBROUTINE+–+
| |Prog file number 5| |
| |Input par 12| |
| |Return par | |
| +––––––––––––––––––+ |
Rung 2:5
This rung is identical to 2:2 except it uses device 2.
| Device 2 Device 2 |
| Device 2 Hart Process |
| STT Done Command # Variable |
| N12:30 +EQU–––––––––––––––+ +MOV–––––––––––––––+ |
+––––] [––––––––––––––––––––––––––++EQUAL +––+MOVE ++–+
| 2 ||Source A N12:5| |Source F13:10|| |
| || 1| | 0.000000|| |
| ||Source B 1| |Dest F15:2|| |
| || | | 0.000000|| |
| |+––––––––––––––––––+ +––––––––––––––––––+| |
| | Device 2 Device 2 | |
| | Hart Hart | |
| | Command # Address | |
| |+EQU–––––––––––––––+ +COP–––––––––––––––+ | |
| ++EQUAL +++COPY FILE +++ |
| ||Source A N12:5|||Source #N12:40||| |
| || 1|||Dest #N12:6||| |
| ||Source B 0|||Length 3||| |
| || ||+––––––––––––––––––+|| |
| |+––––––––––––––––––+| Device 2 || |
| | | Hart || |
| | | Command # || |
| | |+MOV–––––––––––––––+|| |
| | ++MOVE ++| |
| | |Source 1| | |
| | | | | |
| | |Dest N12:5| | |
| | | 1| | |
| | +––––––––––––––––––+ | |
| | Device 2 Device 2 | |
| | Not Hart | |
| | Responding Command # | |
| |+EQU–––––––––––––––+ +MOV–––––––––––––––+| |
| ++EQUAL +––+MOVE ++ |
| |Source A N12:33| |Source 0| |
| | 2| | | |
| |Source B 33| |Dest N12:5| |
| | | | 1| |
| +––––––––––––––––––+ +––––––––––––––––––+ |
Rung 2:6
| |
+––––––––––––––––––––––––––––––––[END OF FILE]–––––––––––––––––––––––––––––––––+
| |