Rockwell Automation 1770,D17706.5.21 SMART TRANSMITTER TOOLKI User Manual

Page 53

background image

Appendix B

Codes

B-3

HART Protocol Communication Error Codes

Integer Word 34

Bit

Error Code

Description

7

Communications Error

If set, the field device has detected a communications error. Bits 0 Ć 6 indicate the type of error.

6

Vertical Parity Error

The parity of one or more of the bytes received by the HART field device is incorrect.

5

Overrun Error

At least one byte of data in the receive buffer of the HART field device was overĆwritten before it

was read.

4

Framing Error

The stop bit of one or more bytes received by the HART field device was not detected.

3

Longitudinal Parity Error

The longitudinal parity calculated by the HART field device does not match the longitudinal parity

byte at the end of the packet.

2

Reserved

Set to 0.

1

Buffer Overflow

The packet is too long for the receive buffer of the HART field device.

0

Undefined

Not defined at this time.

HART Command Response Summary Error Codes

Integer Word 35

Code

HART Command Code Definition

0

All

No commandĆspecific errors

No errors were found in verifying the parameters for this command.

2

All

Invalid Selection

The code or index was not allowed in this command or for this field device.

5

All

Too Few Data Bytes Received The message syntax was proper but the number of bytes contained in the message

was less than required to execute the command.

6

All

TransmitterĆSpecific

Command Error

An error occurred in a HART command for which a CommandĆSpecific Response

Code is not defined. Further information on this response code is available in each

TransmitterĆSpecific document.

7

All

In Write Protect Mode

The field device is Write Protected and cannot accept this write command.

8

All

Warning: Update Failure

The realĆtime data returned from the field device has not changed since the last time

it was read.

9

35

Lower Range Value too High

The Lower Range Value was above the Upper Sensor Limit.

43

Applied Process too High

The process applied to the field device was too high.

10

35

Applied Process too Low

The process applied to the field device was too low.

43

Lower Range Value too Low

The Lower Range Value was below the Lower Sensor Limit.

11

All

Upper Range Value too High

The Upper Range Value was above the Upper Sensor Limit.

12

All

Upper Range Value too Low

The Upper Range Value was below the Lower Sensor Limit.

13

All

Upper and Lower Range

Values Out of Limits

Both the Upper and Lower Range Values are beyond their limits.

14

All

Span too Small

The Span, as determined from the Upper and Lower Range Values, was below the

Minimum Span.

16

All

Access Restricted

The command was rejected due to a condition within the Field Device which would

prevent proper execution.

32

All

Busy

The device is performing a function that cannot be interrupted by this command.

64

All

Command not implemented

The command was not defined for this device.

This code applies to all HART commands that are supported by this release of the Smart Transmitter Toolkit: 0, 1, 3, 35, 38, 43, and 44.