Rockwell Automation 1770,D17706.5.21 SMART TRANSMITTER TOOLKI User Manual
Page 53

Appendix B
Codes
B-3
HART Protocol Communication Error Codes
Integer Word 34
Bit
Error Code
Description
7
Communications Error
If set, the field device has detected a communications error. Bits 0 Ć 6 indicate the type of error.
6
Vertical Parity Error
The parity of one or more of the bytes received by the HART field device is incorrect.
5
Overrun Error
At least one byte of data in the receive buffer of the HART field device was overĆwritten before it
was read.
4
Framing Error
The stop bit of one or more bytes received by the HART field device was not detected.
3
Longitudinal Parity Error
The longitudinal parity calculated by the HART field device does not match the longitudinal parity
byte at the end of the packet.
2
Reserved
Set to 0.
1
Buffer Overflow
The packet is too long for the receive buffer of the HART field device.
0
Undefined
Not defined at this time.
HART Command Response Summary Error Codes
Integer Word 35
Code
HART Command Code Definition
0
All
➀
No commandĆspecific errors
No errors were found in verifying the parameters for this command.
2
All
➀
Invalid Selection
The code or index was not allowed in this command or for this field device.
5
All
➀
Too Few Data Bytes Received The message syntax was proper but the number of bytes contained in the message
was less than required to execute the command.
6
All
➀
TransmitterĆSpecific
Command Error
An error occurred in a HART command for which a CommandĆSpecific Response
Code is not defined. Further information on this response code is available in each
TransmitterĆSpecific document.
7
All
➀
In Write Protect Mode
The field device is Write Protected and cannot accept this write command.
8
All
➀
Warning: Update Failure
The realĆtime data returned from the field device has not changed since the last time
it was read.
9
35
Lower Range Value too High
The Lower Range Value was above the Upper Sensor Limit.
43
Applied Process too High
The process applied to the field device was too high.
10
35
Applied Process too Low
The process applied to the field device was too low.
43
Lower Range Value too Low
The Lower Range Value was below the Lower Sensor Limit.
11
All
➀
Upper Range Value too High
The Upper Range Value was above the Upper Sensor Limit.
12
All
➀
Upper Range Value too Low
The Upper Range Value was below the Lower Sensor Limit.
13
All
➀
Upper and Lower Range
Values Out of Limits
Both the Upper and Lower Range Values are beyond their limits.
14
All
➀
Span too Small
The Span, as determined from the Upper and Lower Range Values, was below the
Minimum Span.
16
All
➀
Access Restricted
The command was rejected due to a condition within the Field Device which would
prevent proper execution.
32
All
➀
Busy
The device is performing a function that cannot be interrupted by this command.
64
All
➀
Command not implemented
The command was not defined for this device.
➀
This code applies to all HART commands that are supported by this release of the Smart Transmitter Toolkit: 0, 1, 3, 35, 38, 43, and 44.