Rockwell Automation 25-COMM-P PowerFlex PROFIBUS DPV1 Adapter User Manual
Page 78
78
Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013
Appendix B
Adapter Parameters
08
[Net Rate Actual]
Displays the actual speed (bps) for the adapter’s Profibus
network port.
Values:
0 = 9.6 Kbps
1 = 19.2 Kbps
2 = 45.45 Kbps
3 = 93.75 Kbps
4 = 187.5 Kbps
5 = 500 Kbps
6 = 1.5 Mbps
7 = 3.0 Mbps
8 = 6.0 Mbps
9 = 12.0 Mbps
10 = Offline
Type:
Read Only
09
[Profibus DP State]
Displays the current state of Profibus DP communications with
the master.
Values:
0 = WAIT_PRM
1 = WAIT_CFG
2 = DATA_EX
3 = ERROR
Type:
Read Only
10
[Profibus Mode]
Displays the Profibus operation mode selected by the user using
the mode selection jumper. This will either be Normal or
PROFIdrive.
Important: PROFIdrive is not supported in this version. It is
reserved for future firmware update.
Values:
0 = Normal
1 = PROFIdrive
Type:
Read Only
11
[Comm Flt Action]
Sets the action that the adapter and drive will take if the
adapter detects that I/O communication has been disrupted.
This setting is effective only if I/O that controls the drive is
transmitted through the adapter. When communication is re-
established, the drive will automatically receive commands
over the network again.
Default:
0 = Fault
Values:
0 = Fault
1 = Stop
2 = Zero Data
3 = Hold Last
4 = Send Flt Cfg
Type:
Read/Write
Reset Required:
No
Parameter
No.
Name and Description
Details
ATTENTION: Risk of injury or equipment damage exists. Device
parameter 11 [Comm Flt Action] lets you determine the action of the
adapter and connected drive if communications are disrupted. By
default, this parameter faults the drive. you can set this parameter so
that the drive continues to run. Precautions should be taken to ensure
that the setting of this parameter does not create a risk of injury or
equipment damage. When commissioning the drive, verify that your
system responds correctly to various situations (for example, a
disconnected drive).