Configuring the rs-485 network – Rockwell Automation 25-COMM-P PowerFlex PROFIBUS DPV1 Adapter User Manual
Page 58

58
Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013
Chapter 7
Using Multi-Drive Mode
Multi-Drive Example of I/O Image
Note:
If a daisy-chained drive is disconnected from the RS-485 (DSI) network
or powered down, the Logic Status and Feedback words for the affected drive will
be set to 0.
Configuring the RS-485
Network
The following parameters must be set in the daisy-chained PowerFlex 4M drives
and not in the master drive:
Note:
The RS-485 Multi-drive network is fixed at 19.2K baud rate, 8 data bits,
no parity, and 1 stop bit.
Controller
Scanner
Adapter
Word and I/O
PROFIBUS
DSI
Output
Image
(Write)
Input
Image
(Read)
Message
Handler
Message
Buffer
Logic Command
Word 0
Reference
Word 1
Drive 0
Logic Command
Word 2
Reference
Word 3
Logic Command
Word 4
Reference
Word 5
Logic Command
Word 6
Reference
Word 7
Logic Command
Word 8
Reference
Word 9
PowerFlex Drive 2
PowerFlex Drive 0
PowerFlex Drive 1
PowerFlex Drive 3
PowerFlex Drive 4
PowerFlex Drive 0
PowerFlex Drive 1
PowerFlex Drive 2
PowerFlex Drive 3
PowerFlex Drive 4
Drive 1
Drive 2
Drive 3
Drive 4
Logic Status
Word 0
Feedback
Word 1
Drive 0
Logic Status
Word 2
Feedback
Word 3
Logic Status
Word 4
Feedback
Word 5
Logic Status
Word 6
Feedback
Word 7
Logic Status
Word 8
Feedback
Word 9
Drive 1
Drive 2
Drive 3
Drive 4
Parameter
Value
P106 [Start Source]
5 “Comm Port”
P108 [Speed Reference]
5 “Comm Port”
C302 [Comm Data Rate]
4 “19.2K”
C303 [Comm Node Addr]
1...247 (must be unique)
C306 [Comm Format]
0 “RTU-8-N-1”