Installing the Adapter
Chapter 2
Drive and Adapter Status Indicators
Configuring/Verifying Key Drive Parameters
The PowerFlex 520-series drive can be separately configured for the control and
Reference functions in various combinations. For example, you could set the
drive to have its control come from a peripheral or terminal block with the
Reference coming from the network. Or you could set the drive to have its
control come from the network with the Reference coming from another
peripheral or terminal block. Or you could set the drive to have both its control
and Reference come from the network.
Configuring the
Host parameters can be done using the drive’s keypad, a HIM,
Logix Designer or Connected Components Workbench. In the following
example, the drive will receive the Logic Command and Reference from the
network.
1.
Set the value of
Host parameter P046 [Start Source 1]
to 4 “Network Opt”.
2.
Set the value of
Host parameter P047 [Speed Reference1]
to 4 “Network Opt”.
Esc
Sel
FWD
ENET LINK
EtherNet/IP
Item
Status Indicator
Status
(1)
(1) If all status indicators are off, the adapter is not receiving power. If any other conditions occur, see
Description
➊
PORT
Green
Normal operation. The adapter is properly
connected and is communicating with the
drive.
Flashing green
The adapter is in the process of establishing a
connection to the drive. This status indicator
will turn solid green or red.
➋
MOD
Green
Normal operation. The adapter is operational
and is transferring I/O data.
Flashing green
Normal operation. The adapter is operational
but is not transferring I/O data.
➌
NET A
Green
Normal operation. The adapter is properly
connected and communicating on the
network.
Flashing green
The adapter is properly connected but is not
communicating with any devices on the
network.
➍
NET B
Off
Not used for PROFIBUS network.
➊
➋
25-COMM-P
PowerFlex 525 Frame A shown
➌
➍
➊
➋
➌
➍