beautypg.com

I/o communication – Rockwell Automation 25-COMM-P PowerFlex PROFIBUS DPV1 Adapter User Manual

Page 44

background image

44

Rockwell Automation Publication 520COM-UM004A-EN-E - November 2013

Chapter 5

Using the I/O

makeup of the I/O connection in a running system. The I/O connection with
the controller must first be disabled to allow changes to the respective Datalinks.

Depending on the controller being used, the I/O connection can be disabled by:

Putting the controller in Program mode

Placing the master in idle mode

Disconnecting the drive from the network

I/O Communication

The following example describes how to use PROFIBUS DPV0 I/O
communication for the CompactLogix controller for the PROFIBUS MVI69-
PDPMV1 Master.

I/O data transferred to and from the 25-COMM-P adapter nodes can be viewed
in the MVI69-PDPMV1 CompactLogix controller tags for the DPV0 cyclic
communication connections. See

Input Mapping in the MVI69-PDPMV1 on

page 44

and

Output Mapping in the MVI69-PDPMV1 on page 45

for input and

output mapping in the MVI69-PDPMV1.

Input Mapping in the MVI69-PDPMV1