Control supervisor object, Overload object – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual
Page 174

B-6 Motor Starter Operation
Publication 198-UM002A-EN-P December 2001
called out in the DeviceNet Motor Starter Profile as “Required” objects in all DeviceNet
Motor Starters. Their definitions are given below.
Control Supervisor Object
CLASS CODE 0x0029
This object only exists for units reporting a product type of 22 (Motor Starter). No class
attributes will be supported.
A single instance (instance 1) of the Control Supervisor Object will be supported. The
following instance attributes will be supported.
The following common services will be implemented for the Control Supervisor Object.
Overload Object
CLASS CODE 0x002c
No class attributes will be supported for the Overload Object.
No instance attributes will be supported for the Overload Object.
No common services will be implemented for the Overload Object.
Table B.8
Attribute ID Access Rule Name
Data Type
Value
1
Get/Set
Run 1
BOOL
Also maps to “Value” attribute of DOP 1
2
Get/Set
Run 2
BOOL
Also maps to “Value” attribute of DOP 2
3
Get
Running 1
BOOL
Also maps to “Value” attribute of DIP 1
4
Get
Running 2
BOOL
Also maps to “Value” attribute of DIP 3
Table B.9
Service Code Implemented for:
Service Name
Class
Instance
0x0E
No
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single