5-67 Specifications
Publication 198-UM002A-EN-P December 2001
198-G1P (Gland Plates)
Gland plates may also be referred to as cable plates. These plates are designed to cover
rectangular holes in standard enclosures and to allow easy power and signal access to the
enclosure.
Electrical
Module Operating Voltage Range
11…25V DC
Module Voltage Rating
24V DC
Module Current Draw
71 mA @ 24V DC
Input Voltage Rating
24V DC (sourced from module)
Input On-State Voltage Range
10…26V DC
Input On-State Current
3.0 mA @ 10V DC
7.2 mA @ 26V DC
Input Off-State Voltage Range
0…5V DC
Input Off-State Current
<1.5 mA
Input Filter — Software
Selectable (with two I/O modules)
Off to On
1, 2, 4, 8, 16 ms
On to Off
1.3, 2, 4, 8, 16 ms
Input Compatibility
IEC 1+
Output Voltage Rating
24V DC
Output Load Current
5 mA per output
Switching Device
Solid-State
Module Isolation
132V AC working Voltage
1500V AC for 1 min.
Environmental
Ambient Temperature
Operating
–25…+40
°
C (–4…+104
°
F)
Storage
–40…+85
°
C (–40…+185
°
F)
Relative Humidity
0…95% non-condensing
Shock
Operating
30 g peak acceleration
Non-Operating
50 g peak acceleration
Operating Vibration
10 g @ 58…2000 Hz
0.060 in. peak-to-peak displacement 2…57 Hz
Per IEC 68-2-6
Approvals
Agency Certification
(when product is marked)
cULus Listed
CE marked for all applicable directives
Table 5.35 198-IB2XOB2S-Q5 Specifications (Continued)