Inverter type distributed starter i/o assemblies, Distributed starter specific devicenet objects – Rockwell Automation 198 Series C Modular DeviceNet Starter Auxiliary User Manual User Manual
Page 173
![background image](/manuals/577535/173/background.png)
Motor Starter Operation B-5
Publication 198-UM002A-EN-P December 2001
Inverter Type Distributed Starter I/O Assemblies
These assemblies are available when the Motor Starter Type parameter is set to the value 3 =
Inverter Starter.
Inverter Type Distributed Starter Output (Consumed) Assemblies
Instance 3 is the required output (consumed) assembly defined in the DeviceNet Motor
Starter Profile.
Instance 154 is the default output (consumed) assembly for Inverter Type Distributed Starters
Inverter Type Distributed Starter Input (Produced) Assemblies
Instance 52 is the required input (produced) assembly defined in the DeviceNet Motor Starter
Profile.
Instance 155 is the default input (produced) assembly for Inverter Type Distributed Starters
Distributed Starter Specific DeviceNet Objects
When a Cat. No. 198-DNG is programmed to present itself as a Distributed Starter on
DeviceNet, two start-specific objects become visible via DeviceNet. These two objects are
Table B.5 Instance 153 — Default Produced Reversing Distributed Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Location 1 Location 0 Status 6
Status 5
Status 4
Status 3
Status 2
Status 1
1
Error 6
Error 5
Error 4
Error 3
Error 2
Error 1
Error 0
Location 2
2
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
3
Input 16
Input 15
Input 14
Input 13
Input 12
Input 11
Input 10
Input 9
4
Input 24
Input 23
Input 22
Input 21
Input 20
Input 19
Input 18
Input 17
Table B.6 Instance 154 — Default Consumed Inverter Type Distributed Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Output 8
Output 7
Output 6
Preset 2
Preset 1
Preset 0
Run Rev
Run Fwd
1
Output 16
Output 15
Output 14
Output 13
Output 12
Output 11
Output 10
Output 9
Table B.7 Instance 155 — Default Produced Inverter Type Distributed Starter
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
Location 1 Location 0 Status 6
Status 5
Status 4
Status 3
Status 2
Status 1
1
Error 6
Error 5
Error 4
Error 3
Error 2
Error 1
Error 0
Location 2
2
Input 8
Input 7
Input 6
Input 5
Input 4
Input 3
Input 2
Input 1
3
Input 16
Input 15
Input 14
Input 13
Input 12
Input 11
Input 10
Input 9
4
Input 24
Input 23
Input 22
Input 21
Input 20
Input 19
Input 18
Input 17