Publication 0160-5.18 - June 2003

B-16

DeviceNet Information

Class Code 0x2A —
AC Drive Object

Instance 1 Attributes

Common Services

Class Attributes: None Supported

Number of Instances: 1

Attribute

ID

Access

Rule

Name

Data

Type

Min/Max

Units

Default

Description

3

Get

AtReference

BOOL 0 to 1

0

Set to 1 when SpeedActual is equal to SpeedRef.

4

Get/Set NetRef

BOOL 0 to 1

0

1 = Drive uses SpeedRef (attribute 8) as its speed reference.
0 = Drive gets its speed reference from local terminal block 3.

6

Get

Drive Mode

USINT 1

1

1 = Open Loop Frequency control.

7

Get

SpeedActual

INT

0 to 32000

1 RPM

0

Actual speed command in RPM.

8

Get/Set SpeedRef

INT

0 to 32000

1 RPM

1800 RPM

Speed reference in RPM.

9

Get

CurrentActual

INT

0 to 32000

0.01 Amp

Actual motor phase current in amperes.

10

Get/Set CurrentLimit

INT

0 to 32000

0.01 Amp 180% of rating Motor phase current limit in amperes.

15

Get

PowerActual

INT

0 to 32000

1 Watt

Actual drive output power in Watts.

16

Get

InputVoltage

INT

0 to 460

1 Volt

230V or 460V Input voltage rating.

17

Get

OutputVoltage

INT

0 to 460

1 Volt

Output voltage to the motor.

18

Get/Set AccelTime

UINT

100 to 65500 1 mSec

10000

Time to accelerate from 0 to HighSpeed Limit.

19

Get/Set DecelTime

UINT

100 to 65500 1 mSec

10000

Time to decelerate from HighSpeed Limit to 0.

20

Get/Set LowSpeed Limit UINT

0 to 32000

1 RPM

0 RPM

Minimum Speed Limit in RPM.

21

Get/Set HighSpeed Limit UINT

0 to 32000

1 RPM

1800 RPM

Maximum Speed Limit in RPM.

29

Get

RefFromNet

BOOL 0 to 1

0

Status of Network Speed Reference.
1 = Drive uses SpeedRef.
0 = Drive uses local reference.

Bulletin

160 SSC

Specific

Extensions

The AC Drive Object includes in its implementation a variable number of 160 SSC specific instance attributes. By adding the number 100 to
any parameter number in the Bulletin 160 parameter table, the resulting number will be a 160 SSC specific instance attribute in the AC Drive
Object. For example, in the 160 SSC drive, parameter 5 displays Bus Voltage. Therefore, attribute # 105 of the AC Drive Object returns Bus
Voltage. This method of extending the AC Drive Object allows for an ODVA compliant implementation of the Drive Profile, and
accommodates all Bulletin 160 SSC models (both analog and preset speed models). Refer to the Bulletin 160 SSC User Manual, Chapter 5.

Service

Code

Implemented for:

Service

Name

Class

Instance

0x0E

No

Yes

Get_Attribute_Single

0x10

No

Yes

Set_Attribute_Single