Class code 0xb3 - 160 parameter table object, B-18, B-18 b-18 b-18 – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual
Page 100
Publication 0160-5.18 - June 2003
B-18
DeviceNet Information
Class Code 0xB3 —
160 Parameter Table Object
Instance 1 Attributes
Class Attributes: None Supported
Number of Instances: 1
Attribute ID
Access
Rule
Parameter Name
Data
Type
Units
Description
This Bulletin 160 SSC specific object implements all of the parameters in the 160 SSC parameter table as instance attributes of the object. For example,
attribute #1 corresponds to P01 - [Output Frequency]. This enables you to configure a drive via DeviceNet using attribute numbers that are published as
parameter numbers in the Bulletin 160 SSC User Manual.
Important: Attributes 9 and 12 shown below do not match what is published in the Bulletin 160 SSC User Manual.
01
Get
[Output Frequency]
UINT
0.1 Hz
Frequency at TB2 terminals T1, T2, T3.
02
Get
[Output Voltage]
UINT
1 Volt
Voltage at TB2 terminals T1, T2, T3.
03
Get
[Output Current]
UINT
0.01 Amperes
Current at TB2 terminals T1, T2, T3.
04
Get
[Output Power]
UINT
0.01 kW
Power at TB2 terminals T1, T2, T3.
05
Get
[Bus Voltage]
UINT
1 Volt
DC Bus voltage level.
06
Get
[Cmd Frequency]
UINT
0.1 Hz
Commanded frequency.
07
Get
[Present Fault]
USINT
Numeric Value
Coded last fault number.
08
Get
[Heatsink Temp]
USINT
1 C
Temperature of the drive heatsink.
09
Get
[Drive Status]
WORD
Binary Number
Status of drive in binary coded format.
10
Get
[Drive Type]
USINT
Numeric Value
Used by Allen-Bradley field service personnel.
11
Get
[Control Version]
UINT
Numeric Value
version of drive firmware used.
12
Get
[Input Status]
WORD
Binary Number
Open (0) Closed (1) state of drive’s discrete inputs.
13
Get
[Power Factor Ang]
UINT
0.1
Angle (electrical degrees) between V and I.
14
Get
[Memory Probe]
UINT
Numeric Value
Used by Allen-Bradley service personnel.
15
Get
[Preset Status]
WORD
Binary Number
Displays state of TB3 inputs.
16
Get
[Analog Input]
INT
0.1%
The analog input as a percent of full scale.
17
Get
[Fault Buffer 0]
USINT
Numeric Value
Stores the most recent fault.
18
Get
[Fault Buffer 1]
USINT
Numeric Value
Stores the second most recent fault.
19
Get
[Fault Buffer 2]
USINT
Numeric Value
Stores the third most recent fault.
30
Get/Set
[Accel Time 1]
UINT
0.1 Seconds
Time to ramp from 0 Hz to maximum frequency.
31
Get/Set
[Decel Time 1]
UINT
0.1 Seconds
Time to ramp from maximum frequency to 0 Hz.
32
Get/Set
[Minimum Freq]
USINT
1 Hz
Lowest continuous output frequency.
33
Get/Set
[Maximum Freq]
UINT
1 Hz
Highest continuous output frequency.
34
Get/Set
[Stop Mode Select]
USINT
Numeric Value
Determines stop mode used.
!
ATTENTION: Changing this parameter
value may cause unpredictable network
conditions, resulting in equipment damage,
personal injury, or death. Make sure that
you understand how changing this
parameter affects your application.