Drive program parameters (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual
Page 37
Publication 0160-5.18 - June 2003
DeviceNet Parameter Descriptions
5-9
Drive Program Parameters
(Continued)
Parameter
Number
Parameter Name
Object Mapping
(Class-Instance-
Attribute)
Description
Units
54
[Clear Fault]
0xB3-1-54
Setting to 1 performs a fault reset.
Numeric Value
55
[Probe Address]
0xB3-1-55
Used by Allen-Bradley service personnel.
Numeric Value
56
[Reset Functions]
0xB3-1-56
Sets all parameters to their factory default.
Numeric Value
57
[Program Lock]
0xB3-1-57
Locks all program group parameters.
Numeric Value
58
[Internal Freq]
0xB3-1-58
Digital frequency setpoint.
0.1 Hz
59
[Freq Select]
0xB3-1-59
Selects source of Frequency command.
Numeric Value
60
[Zero Offset]
0xB3-1-60
Add or subtracts an offset to the analog input.
Numeric Value
60
[DN Preset Cmd]
0xB3-1-92
Network preset command.
Numeric Value
61
[Preset Freq 0]
0xB3-1-61
Sets command frequency when selected.
0.1 Hz
62
[Preset Freq 1]
0xB3-1-62
Sets command frequency when selected.
0.1 Hz
63
[Preset Freq 2]
0xB3-1-63
Sets command frequency when selected.
0.1 Hz
64
[Preset Freq 3]
0xB3-1-64
Sets command frequency when selected.
0.1 Hz
65
[Preset Freq 4]
0xB3-1-65
Sets command frequency when selected.
0.1 Hz
66
[Preset Freq 5]
0xB3-1-66
Sets command frequency when selected.
0.1 Hz
67
[Preset Freq 6]
0xB3-1-67
Sets command frequency when selected.
0.1 Hz
68
[Preset Freq 7]
0xB3-1-68
Sets command frequency when selected.
0.1 Hz
69
[Accel Time 2]
0xB3-1-69
Sets second acceleration rate.
0.1 Seconds
70
[Decel Time 2]
0xB3-1-70
Sets second deceleration rate.
0.1 Seconds
71
[IR Compensation]
0xB3-1-71
Adds a voltage to the output based on the torque current.
1%
72
[Slip Comp]
0xB3-1-72
Compensates for the inherent slip of the motor.
0.1 Hz
73
[Reverse Disable]
0xB3-1-73
Setting to 1 disables the reverse.
Numeric Value
74
[Analog Select]
0xB3-1-74
Selects between unipolar and bipolar analog input.
Numeric Value
75
[Analog Minimum]
0xB3-1-75
Sets the percent of the analog input used to represent
P32 - [Minimum Frequency].
0.1%
76
[Analog Maximum]
0xB3-1-76
Sets the percent of the analog input used to represent
P33 - [Maximum Frequency].
0.1%
78
[Compensation]
0xB3-1-78
Some drive/motor combinations have inherent instabilities
which are exhibited as non-sinusoidal motor currents. A
setting of 1 will enable the compensation to correct this
condition. A setting of 0 disables this function.
Numeric Value
79
[Curent Trip]
0xB3-1-79
Percent above P43 - [Current Limit] at which the drive trips
immediately.
1%
This parameter applies only to the Analog Signal Follower model.
This parameter applies only to the Preset Speed model.