beautypg.com

Drive program parameters (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 38

background image

Publication 0160-5.18 - June 2003

5-10

DeviceNet Parameter Descriptions

Drive Program Parameters
(Continued)

Parameter

Number

Parameter Name

Object Mapping

(Class-Instance-

Attribute)

Description

Units

80

[Stall Disable]

0xB3-1-80

Amount of time that the drive must be in a stall condition
before it causes a stall fault.

Numeric Value

81

[Proc Kp Gain]

0xB3-1-81

Proportional gain used by the PI regulator. This parameter is
active when P46 - [Input Mode] setting 9 is used.

Numeric Value

82

[Proc Ki Gain]

0xB3-1-82

Integral gain used by the PI regulator. This parameter is
active when P46 - [Input Mode] setting 9 is used.

Numeric Value

83

[Proc Reference]

0xB3-1-83

Set point value to which PI control will regulate. This
parameter is active when P46 - [Input Mode] setting 9 is
used.

Numeric Value

84

[PI Dead Band]

0xB3-1-84

The PI control will ignore errors less than this value. This
parameter is active when P46 - [Input Mode] setting 9 is
used.

Numeric Value

This parameter applies only to the Analog Signal Follower model.

This parameter applies only to the Preset Speed model.

!

ATTENTION: Risk of equipment damage
exists. Continuous operation at high
currents caused by a stall can cause motor
damage.