Instance data format: output assemblies, B-24, Class code 0x04 — assembly objects (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 106

background image

Publication 0160-5.18 - June 2003

B-24

DeviceNet Information

Class Code 0x04 —
Assembly Objects (Continued)

Instance Data Format: Output Assemblies

➀ If speed references are outside of their min/max limits, the drive ignores them and previous speed references will be maintained.
➁ 0 – 32000 RPM. The RPM value is limited by the value programmed into P33 - [Maximum Frequency].
➂ Must set bit 5 and bit 6 high before issuing bit 0 or bit 1.
➃ If bit is set to a 0, the drive looks to TB2 for speed reference control. If bit is set to 1, the drive looks to the network for speed reference control.
➄ If bit is set to 0 (low), parameter 118 will pass its value to parameter 46. If bit is set to 1 (high), parameter 118 will be ignored, and parameter 46 will stay

“network control.”

➅ 0 = 0 Hz, 2400 = 240.0 Hz. The frequency value is limited by the value programmed into P33 - [Maximum Frequency].

Instance 1 Data Format (Basic Contactor Output Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Run

Instance 2 Data Format (Basic Overload Output Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault Reset

Instance 3 Data Format (Basic Motor Starter Output Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault Reset

Run

Instance 4 Data Format (Extended Contactor Output Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

RunRev

RunFwd

Instance 5 Data Format (Extended Motor Starter Output Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault Reset

RunRev

RunFwd

Instance 20 Data Format (Basic Speed Control Output Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault Reset

RunFwd

1

2

Speed Reference RPM (Low Byte)

3

Speed Reference RPM (High Byte)

Instance 21 Data Format (Reversing Speed Control Output Assembly)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

NetRef

➂➃

Net Control

➂➄

Fault Reset

RunRev

RunFwd

1

2

Speed Reference RPM (Low Byte)

3

Speed Reference RPM (High Byte)

Instance 100 Data Format (Reversing Speed Control Output Assembly (Hz)

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Fault Reset

RunRev

RunFwd

1

2

Internal Frequency (0.1 Hz) (Low Byte)

3

Internal Frequency (0.1 Hz) (High Byte)