Class code 0x05 — connection object (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual
Page 90
![background image](/manuals/577375/90/background.png)
Publication 0160-5.18 - June 2003
B-8
DeviceNet Information
Class Code 0x05 —
Connection Object (Continued)
Instance 4 Attributes: Change of State/Cyclic Instance
Common Services
Attribute ID
Access Rule
Name
Data Type
Value
1 Get
State
USINT
0 = Nonexistant
1 = Configuring
3 = Established
4 = Timed out
2
Get
Instance Type
USINT
1 = I/O Message
3
Get
Transport Class Trigger
USINT
0x82
4 Get
Produced
Connection
ID
UINT
10xxxxxx100
where xxxxxx = Node address
5
Get
Consumed Connection ID
UINT
10xxxxxx101
where xxxxxx = Node address
6
Get
Initial Comm Characteristics
USINT
0x21
7
Get
Produced Connection Size
UINT
0 to 8
8
Get
Consumed Connection Size
UINT
0 to 4
9
Get/Set
Expected Packet Rate
UINT
timer resolution of 10 msec.
12 Get/Set
Watchdog
Action
USINT
0 = transition to timed out
1 = auto delete
2 = auto reset
13
Get
Produced Connection Path Length
UINT
3
14 Get/Set
Produced
Connection
Path
[63hex][hex string]
where [hex string] is the input assembly
number in hex
15
Get
Consumed Connection Path Length
UINT
3
16
Get/Set
Consumed Connection Path
[63hex][hex string]
where [hex string] is the output
assembly number in hex
17
Get/Set
Production Inhibit Time
UINT
0
Service
Code
Implemented for:
Service
Name
Class
Instance
0x05
No
Yes
Reset
0x0E
Yes
Yes
Get_Attribute_Single
0x10
No
Yes
Set_Attribute_Single