beautypg.com

Configuration assembly data formats, B-29, Class code 0x04 — assembly objects (continued) – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual

Page 111

background image

Publication 0160-5.18 - June 2003

DeviceNet Information

B-29

Class Code 0x04 —
Assembly Objects (Continued)

Configuration Assembly Data Formats

Instance 191 Data Format (Fixed Configuration Assembly – All Preset Speed Models)

Config Num.

Parameter

Number

Description

Size

Config Num.

Parameter

Number

Description

Size

1

30

Accel Time 1

2

17

46

Input Mode

1

2

31

Decel Time 1

2

18

47

Output Configuration

1

3

32

Minimum Freq

1

19

48

Output Threshold

2

4

33

Maximum Freq

2

20

49

PWM Frequency

1

5

34

Stop Mode Select

1

21

50

Restart Tries

1

6

35

Base Frequency

2

22

51

Restart Time

2

7

36

Base Voltage

2

23

61

Preset Freq 0

2

8

37

Maximum Voltage

2

24

62

Preset Freq 1

2

9

38

Boost Select

1

25

63

Preset Freq 2

2

10

39

Skip Frequency

2

26

64

Preset Freq 3

2

11

40

Skip Freq Band

1

27

65

Preset Freq 4

2

12

41

Overload Select

1

28

66

Preset Freq 5

2

13

42

Motor Overload

2

29

67

Preset Freq 6

2

14

43

Current Limit

1

30

68

Preset Freq 7

2

15

44

DC Hold Time

1

31

69

Accel Time 2

2

16

45

DC Hold Voltage

1

32

70

Decel Time 2

2

!

!

Instance 192 Data Format (Fixed Configuration Assembly – All Signal Follower Models)

Config Num.

Parameter

Number

Description

Size

Config Num.

Parameter

Number

Description

Size

1

30

Accel Time 1

2

13

42

Motor Overload

2

2

31

Decel Time 1

2

14

43

Current Limit

1

3

32

Minimum Frequency

1

15

44

DC Hold Time

1

4

33

Maximum Frequency

2

16

45

DC Hold Voltage

1

5

34

Stop Mode Select

1

17

46

Input Mode

1

6

35

Base Frequency

2

18

47

Output Configuration

1

7

36

Base Voltage

2

19

48

Output Threshold

2

8

37

Maximum Voltage

2

20

49

PWM frequency

1

9

38

Boost Select

1

21

50

Restart Tries

1

10

39

Skip Frequency

2

22

51

Restart Time

2

11

40

Skip Freq Band

1

23

53

S-Curve

1

12

41

Overload Select

1

!

!

!

ATTENTION: Changing this parameter value may cause unpredictable network conditions, resulting in equipment damage, personal injury, or death.
Ensure that you understand how changing this parameter affects your application.