Run mode, Error mode, Run mode -2 error mode -2 – Rockwell Automation 160-DN2 160-DN2 DeviceNet Communication Module FRN 3.xx User Manual
Page 28: Modes of operation (continued)
Publication 0160-5.18 - June 2003
4-2
Modes of Operation
Modes of Operation (Continued)
Power-up Reset Mode (Continued)
If the power up or reset sequence fails, the COMM LED will turn
solid red and the 160-DN2 module will enter the Error mode (see
heading below for more information).
Run Mode
After a successful power-up or reset, the 160-DN2 module enters the
run mode and operates as a slave device to a master device. In run
mode, the module:
• Accepts messages from the master on the DeviceNet network.
• Monitors DeviceNet incoming power.
If an error is detected, the 160-DN2 module will enter the Error mode
(see heading below for more information).
Error Mode
If the 160-DN2 module detects an error, the COMM LED is affected.
Errors are critical or noncritical, and are summarized below.
See
for details in the troubleshooting
chart on how to recover from an error.
Table 4.A COMM LED State During Power-up Reset Mode
COMM LED State
Description
Flashes Green 1/4 second,
Red 1/4 second,
then goes blank
Occurs when power is applied to module.
Blank
Power-up initialization is taking place.
Solid Red
160-DN2 module is in Error mode. Indicates failed
initialization, duplicate node address or incorrect baud rate.
Solid Green
160-DN2 module is in the Run mode.
Table 4.B COMM LED State During Error Mode
COMM LED State
Error Type
Description
Solid Red
Critical
(not recoverable)
Power-up initialization failure.
Duplicate node address detected.
Incorrect baud rate.
Flashing Red
Non-Critical
(recoverable)
I/O connection timed out.
Off
Non-Critical
(recoverable)
DeviceNet power lost.