Instance attributes, continued – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual
Page 61
Publication 825-UM002A-EN-P - December 2000
A-39
Instance Attributes, Continued
➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.
➋ Available with SMM version 2.xx (and lower).
Attribute
ID
Access
Rule
Name (param. #)
Data
Type
Min/Max
Units
Default
Description
136
Get/Set
warm_st_ (#70)
BOOL
0…1
0=OFF
0
Warm start, on/off
137
Get/Set
warm_tim (#71)
USINT
4…60
minutes
60
Warm start allowed every … minutes
138
Get/Set
wa_trip_ (#72)
USINT
50…100
%
70
Warm start tip time,% trip time from cold
139
Get/Set
start_in (#73)
BOOL
0…1
0=OFF
0
Limiting the number of starts/h, on/off
140
Get/Set
start/h_ (#74)
USINT
1…10
starts/hr
2
Maximum starts/h
141
Get/Set
st_contr (#76)
BOOL
0…1
0=OFF
0
Monitoring start time (start inhibit) on/off
142
Get/Set
st_time_ (#77)
USINT
1…240
seconds
10
Maximum starting time
143
Get/Set
autrs_th (#80)
BOOL
0…1
0=man.
0
Thermal trip reset, automatic/manual
144
Get/Set
th_res_l (#81)
USINT
10…100
%
50
Thermal trip reset at …% of therm.
utilize.
145
Get/Set
cool_rat (#82)
USINT
10…50
0.1
25
Cooling constant ratio, motor off/on
(1.0…5.0)
146
Get/Set
dis_ass1 (#93)
BOOL
0…1
1=disabl
0
Asymmetry protection, enabled/disabled
147
Get/Set
dis_ol_1 (#94)
BOOL
0…1
1=disabl
0
Overcurrent/locked rotor protection,
enabled/disabled
148
Get/Set
dis_ess1 (#95)
BOOL
0…1
1=disabl
0
Earth fault protection, enabled/disabled
149
Get/Set
dis_kss1 (#96)
BOOL
0…1
1=disabl
0
Short circuit protection, enabled/disabled
150
Get/Set
dis_uls1 (#97)
BOOL
0…1
1=disabl
0
Underload protection, enabled/disabled
151
Get/Set
dis_sti1 (#98)
BOOL
0…1
1=disabl
0
Limiting the starts per hour, enabled/
disabled
152
Get/Set
new_flc_ (#105)
BOOL
0…1
0=OFF
0
2
nd
rated motor current, on/off
153
➊
Get/Set
new_Ie__ (#106)
UDINT
50…200,000 10 mA
2000
2
nd
rated motor current, value
(0.50…2000.00 A)
153
➋
Get/Set
new_Ie__ (#106)
UINT
50…63,000
10 mA
2000
2
nd
rated motor current, value
(0.50…630.00 A)
154
Get/Set
dis_ass2 (#108)
BOOL
0…1
1=disabl
0
Asymmetry protection, enabled/disabled
155
Get/Set
dis_ol_2 (#109)
BOOL
0…1
1=disabl
0
Overcurrent/locked rotor protection,
enabled/disabled
156
Get/Set
dis_ess2 (#110)
BOOL
0…1
1=disabl
0
Earth fault protection, enabled/disabled
157
Get/Set
dis_kss2 (#111)
BOOL
0…1
1=disabl
0
Short circuit protection, enabled/disabled
158
Get/Set
dis_uls2 (#112)
BOOL
0…1
1=disabl
0
Underload protection, enabled/disabled
159
Get/Set
dis_sti2 (#113)
BOOL
0…1
1=disabl
0
Limiting the starts per hour, enabled/
disabled