Publication 825-UM002A-EN-P - December 2000

A-39

Instance Attributes, Continued

➊ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination only.

➋ Available with SMM version 2.xx (and lower).

Attribute

ID

Access

Rule

Name (param. #)

Data
Type

Min/Max

Units

Default

Description

136

Get/Set

warm_st_ (#70)

BOOL

0…1

0=OFF

0

Warm start, on/off

137

Get/Set

warm_tim (#71)

USINT

4…60

minutes

60

Warm start allowed every … minutes

138

Get/Set

wa_trip_ (#72)

USINT

50…100

%

70

Warm start tip time,% trip time from cold

139

Get/Set

start_in (#73)

BOOL

0…1

0=OFF

0

Limiting the number of starts/h, on/off

140

Get/Set

start/h_ (#74)

USINT

1…10

starts/hr

2

Maximum starts/h

141

Get/Set

st_contr (#76)

BOOL

0…1

0=OFF

0

Monitoring start time (start inhibit) on/off

142

Get/Set

st_time_ (#77)

USINT

1…240

seconds

10

Maximum starting time

143

Get/Set

autrs_th (#80)

BOOL

0…1

0=man.

0

Thermal trip reset, automatic/manual

144

Get/Set

th_res_l (#81)

USINT

10…100

%

50

Thermal trip reset at …% of therm.
utilize.

145

Get/Set

cool_rat (#82)

USINT

10…50

0.1

25

Cooling constant ratio, motor off/on
(1.0…5.0)

146

Get/Set

dis_ass1 (#93)

BOOL

0…1

1=disabl

0

Asymmetry protection, enabled/disabled

147

Get/Set

dis_ol_1 (#94)

BOOL

0…1

1=disabl

0

Overcurrent/locked rotor protection,
enabled/disabled

148

Get/Set

dis_ess1 (#95)

BOOL

0…1

1=disabl

0

Earth fault protection, enabled/disabled

149

Get/Set

dis_kss1 (#96)

BOOL

0…1

1=disabl

0

Short circuit protection, enabled/disabled

150

Get/Set

dis_uls1 (#97)

BOOL

0…1

1=disabl

0

Underload protection, enabled/disabled

151

Get/Set

dis_sti1 (#98)

BOOL

0…1

1=disabl

0

Limiting the starts per hour, enabled/
disabled

152

Get/Set

new_flc_ (#105)

BOOL

0…1

0=OFF

0

2

nd

rated motor current, on/off

153

Get/Set

new_Ie__ (#106)

UDINT

50…200,000 10 mA

2000

2

nd

rated motor current, value

(0.50…2000.00 A)

153

Get/Set

new_Ie__ (#106)

UINT

50…63,000

10 mA

2000

2

nd

rated motor current, value

(0.50…630.00 A)

154

Get/Set

dis_ass2 (#108)

BOOL

0…1

1=disabl

0

Asymmetry protection, enabled/disabled

155

Get/Set

dis_ol_2 (#109)

BOOL

0…1

1=disabl

0

Overcurrent/locked rotor protection,
enabled/disabled

156

Get/Set

dis_ess2 (#110)

BOOL

0…1

1=disabl

0

Earth fault protection, enabled/disabled

157

Get/Set

dis_kss2 (#111)

BOOL

0…1

1=disabl

0

Short circuit protection, enabled/disabled

158

Get/Set

dis_uls2 (#112)

BOOL

0…1

1=disabl

0

Underload protection, enabled/disabled

159

Get/Set

dis_sti2 (#113)

BOOL

0…1

1=disabl

0

Limiting the starts per hour, enabled/
disabled