beautypg.com

Parameters supported, continued – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 38

background image

Publication 825-UM002A-EN-P - December 2000

A-16

Parameters Supported, Continued

Parameter

No.

Parameter

Name

Object

Mapping

Description

Data
Type

Units

Min/
Max

Default

27

Th Warning Relay 0x29-1-101

Thermal Warning Relay Assignment

USINT

1…7

1

28

Asymmetry Trip

0x2C-1-109

Asymmetry Protection, 0=OFF 1=ON

BOOL

0…1

1

29

As Trip Level

0x2C-1-110

Asymmetry Trip Level

USINT

%

5…80

35

30

As Trip Delay

0x2C-1-111

Asymmetry Trip Delay Time

USINT

0.1 s

10…250 25

31

As Trip Relay

0x29-1-102

Asymmetry Trip Relay Assignment

USINT

0…7

0

32

As Warning

0x2C-1-112

Asymmetry Warning, 0=OFF 1=ON

BOOL

0…1

0

33

As Warning Level 0x2C-1-113

Asymmetry Warning Level

USINT

%

5…80

20

34

As Warning Relay 0x29-1-103

Asymmetry Warning Relay Assignment

USINT

1…7

1

35

Overcurrent Trip

0x2C-1-114

Overload/Locked Rotor Protection 0=OFF
1=ON

BOOL

0…1

1

36

OC Trip Level

0x2C-1-115

Overload/Locked Rotor Trip Level (1.0…6.0
times FLC)

USINT

times
0.1FLC

10…60

24

37

OC Trip Delay

0x2C-1-116

Overload/Locked Rotor Trip Delay Time
(0.1…5.0 sec)

USINT

0.1 s

1…50

5

38

OC Trip Relay

0x29-1-104

Overload/Locked Rotor Relay Assignment

USINT

0…7

0

39

OC Warning

0x2C-1-117

Overload/Locked Rotor Warning, 0 = OFF
1=ON

BOOL

0…1

0

40

OC Warning Level 0x2C-1-118

Overload/Locked Rotor Warning Level
(1.0…6.0 *FLC)

USINT

times
0.1FLC

10…60

20

41

OC Warning Relay 0x29-1-105

Overload/Locked Rotor Warning Relay
Assignment

USINT

1…7

1

42

Earth Fault Prot

0x2C-1-119

Earth Fault Protection, 0=OFF 1=ON

BOOL

0…1

1

43

EF Holmg Trip

0x2C-1-120

Earth Fault Protection (Holmgreen), 0=OFF
1=ON

BOOL

0…1

1

44

EF H Trip Level

0x2C-1-121

Earth Fault Protection (Holmgreen), Trip Level USINT

%Current

10…100 50

45

EF H Trip Delay

0x2C-1-122

Earth Fault Protection (Holmgreen), Trip
Delay Time

USINT

0.1 s

1…50

5

46

EF H Trip Relay

0x29-1-106

Earth Fault Protection (Holmgreen), Relay
Assignment

USINT

0…7

0

47

EF Core Prot

0x2C-1-123

Earth Fault (core balance) Protection,
0=OFF 1=ON

BOOL

0…1

0

48

EF C Trip Level

0x2C-1-124

Earth Fault (core balance) Trip Level

UINT

mA

5…50,00
0

1000

49

EF C Trip Delay

0x2C-1-125

Earth Fault (core balance) Trip Delay Time
(0.1…5.0 s)

USINT

0.1 s

1…50

5

50

EF C Trip Relay

0x29-1-107

Earth Fault (core balance) Trip Relay
Assignment

USINT

0 t0 7

0

This manual is related to the following products: