Parameters supported, continued – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 39

background image

Publication 825-UM002A-EN-P - December 2000

A-17

Parameters Supported, Continued

Parameter

No.

®=read-only

Parameter Name

Object

Mapping

Description

Data
Type

Units

Min/Max Default

51

EF C Warning

0x2C-1-126

Earth Fault (core balance) Trip, Warning,
0=OFF 1=ON

BOOL

0…1

0

52

EF C Warn Level

0x2C-1-127

Earth Fault (core balance) Warning, Level

UINT

mA

5…50,000 500

53

EF C Warn Relay

0x29-1-108

Earth Fault (core balance) Warning, Relay
Assignment

USINT

1…7

1

54

Short Circ Trip

0x2C-1-128

Short Circuit Protection, 0=OFF 1=ON BOOL

0…1

0

55

SC Trip Level

0x2C-1-129

Short Circuit Trip Level (4.0…12.0 times
FLC)

USINT

times
0.1FLC

40…120

100

56

SC Trip Delay

0x2C-1-130

Short Circuit Trip Delay Time

USINT

10 ms

2…99

5

57

SC Trip Relay

0x29-1-109

Short Circuit Relay Assignment

USINT

2, 7

2

58

Underload Trip

0x2C-1-131

Underload Protection, 0=OFF 1=ON BOOL

0…1

0

59

UL Trip Level

0x2C-1-132

Underload Trip Level

USINT

% FLC

25…100

75

60

UL Trip Delay

0x2C-1-133

Underload Trip Delay Time

USINT

seconds 1…60

10

61

UL Trip Relay

0x29-1-110

Underload Trip Relay Assignment

USINT

0…7

0

62

UL Start Delay

0x2C-1-134

Underload Trip Start Delay

USINT

seconds 0…240

0

63

UL Warning

0x2C-1-135

Underload Warning, 0=OFF 1=ON BOOL

0…1

0

64

UL Warning Relay

0x29-1-111

Underload Warning, Relay Assignment

USINT

1…7

1

65

Star Delta

0x29-1-112

Star-Delta Starting, 0=OFF 1=ON

BOOL

0…1

0

66

®

Star Relay

0x29-1-113

Star-Delta Starting, Star Relay

USINT

5

5

67

®

Delta Relay

0x29-1-114

Star-Delta Starting, Delta Relay

USINT

6

6

68

Set Star Time

0x29-1-115

Star-Delta Starting, Max. Star-Time,
0=OFF 1=ON

BOOL

0…1

0

69

Max. Star Time

0x29-1-116

Star-Delta Starting, Max. Star-Time,

USINT

s

1…240

10

70

Warm Starting

0x2C-1-136

Warm Start 0=OFF 1=ON

BOOL

0…1

0

71

Warm Start Every

0x2C-1-137

Warm Start Allowed Every ___ Minutes

USINT

minutes 4…60

60

72

Warm Trip Time

0x2C-1-138

Warm Start Trip Time, as % of Tripping
Time From Cold

USINT

%

50…100

70

73

Start Inhibit

0x2C-1-139

Limiting the Number of Starts/Hour,
0=OFF 1=ON

BOOL

0…1

0

74

Max Starts/Hour

0x2C-1-140

Maximum number of Starts/Hour

USINT

Starts/
hr

1…10

2

75

Start Inhib Rel

0x29-1-117

Maximum Starts/Hour, Relay Assignment

USINT

0…7

0

76

Start Control

0x2C-1-141

Monitoring Starting Time, 0=OFF 1=ON

BOOL

0…1

0