Instance attributes – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual
Page 59
Publication 825-UM002A-EN-P - December 2000
A-37
1XPEHU RI ,QVWDQFHV
Instance Attributes
➊ Bit definitions given on page A-40.
➋ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination.
➌ Available with SMM version 2.xx ( and lower).
Attribute
ID
Access
Rule
Name (param. #)
Data
Type
Min/Max
Units
Default
Description
1
Get
numAttr
USINT
Number of Attributes supported
2
Get
Attributes
Array
USINT
List of attributes supported by the
Overload
3
➋
Set/Get
le________ (#21)
UDINT
30…200,000 10 mA
2000
FLC Setting Value
3
➌
Set/Get
le________ (#21)
UINT
50…63,000
10 mA
2000
FLC Setting Value
165
Set/Get
t_block_ (#23)
UINT
1…600
seconds
10
Max Stall Time
5
Get
lmotor__ (#1))
INT
0…1200
% FLC
0
Average Motor Current
6
Get
Asymetry (#7)
USINT
0…100
%
0
% Asymmetry
7
Get
Th.Util_ (#2)
USINT
0…100
%
0
% Thermal Utilization
8
Get
lmot__L1 (#3)
INT
0…1200
% FLC
0
I phase L1
9
Get
lmot__L2 (#4)
INT
0…1200
% FLC
0
I phase L2
10
Get
lmot__L3 (#5)
INT
0…1200
% FLC
0
I phase L3
11
Get
learth_S (#9)
UINT
0…55000
.005 Amps 0
Earth Core
102
Get
Time_to_ (#6)
UINT
1…9999
seconds
9999
Time to Trip/Reset
103
Get
Iearth_H (#8)
USINT
0…100
%
0
Earth-fault current (Holmgreen)
104
➊
Get
iAUSL___ (#18)
WORD
0…0xffff
bits
0
Actual Trip Bit String (Bit Pattern)
105
➊
Get
iVORW___ (#19)
WORD
0…0xffff
bits 0
Actual
Warning
Bit
String
(Bit
Pattern)
106
Get/Set
Ibl/Ie__ (#22)
USINT
25…120
times
0.1*FLC
60
Locked rotor current (2.5…12.0 times FLC)
107
Get/Set
th_alarm (#25)
BOOL
0…1
0=OFF
0
Thermal warning, on/off
108
Get/Set
th_al_le (#26)
USINT
50…99
%
75
Thermal warning level