Instance attributes – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual

Page 59

background image

Publication 825-UM002A-EN-P - December 2000

A-37

1XPEHU RI ,QVWDQFHV

Instance Attributes

➊ Bit definitions given on page A-40.

➋ Available with SMM version 3.11 (or higher) / 825-MDN version 6.001 (or higher) product combination.

➌ Available with SMM version 2.xx ( and lower).

Attribute

ID

Access

Rule

Name (param. #)

Data
Type

Min/Max

Units

Default

Description

1

Get

numAttr

USINT

Number of Attributes supported

2

Get

Attributes

Array
USINT

List of attributes supported by the
Overload

3

Set/Get

le________ (#21)

UDINT

30…200,000 10 mA

2000

FLC Setting Value

3

Set/Get

le________ (#21)

UINT

50…63,000

10 mA

2000

FLC Setting Value

165

Set/Get

t_block_ (#23)

UINT

1…600

seconds

10

Max Stall Time

5

Get

lmotor__ (#1))

INT

0…1200

% FLC

0

Average Motor Current

6

Get

Asymetry (#7)

USINT

0…100

%

0

% Asymmetry

7

Get

Th.Util_ (#2)

USINT

0…100

%

0

% Thermal Utilization

8

Get

lmot__L1 (#3)

INT

0…1200

% FLC

0

I phase L1

9

Get

lmot__L2 (#4)

INT

0…1200

% FLC

0

I phase L2

10

Get

lmot__L3 (#5)

INT

0…1200

% FLC

0

I phase L3

11

Get

learth_S (#9)

UINT

0…55000

.005 Amps 0

Earth Core

102

Get

Time_to_ (#6)

UINT

1…9999

seconds

9999

Time to Trip/Reset

103

Get

Iearth_H (#8)

USINT

0…100

%

0

Earth-fault current (Holmgreen)

104

Get

iAUSL___ (#18)

WORD

0…0xffff

bits

0

Actual Trip Bit String (Bit Pattern)

105

Get

iVORW___ (#19)

WORD

0…0xffff

bits 0

Actual

Warning

Bit

String

(Bit

Pattern)

106

Get/Set

Ibl/Ie__ (#22)

USINT

25…120

times
0.1*FLC

60

Locked rotor current (2.5…12.0 times FLC)

107

Get/Set

th_alarm (#25)

BOOL

0…1

0=OFF

0

Thermal warning, on/off

108

Get/Set

th_al_le (#26)

USINT

50…99

%

75

Thermal warning level