Instance attributes – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual
Page 55
Publication 825-UM002A-EN-P - December 2000
A-33
Instance Attributes
Attribute
ID
Access
Rule
Name (param #)
Data
Type
Min/Max
Default
Description
1
Get
num Attributes
USINT
See Run/Stop Event Matrix
2
Get
Attributes
Array of
USINT
List of Attributes supported by Control
Supervisor
10
Get
Faulted/Trip (#211)
BOOL
0…1
0
1=Fault Latched
0=No Faults present
11
Get
Warning (#212)
BOOL
0…1
0
1= Warning (not latched)
0=No Warnings present
12
Get/Set
FaultRst (#154)
BOOL
0…1
0
0 -> 1 = Fault Reset
0 = No Action
*13
Get
FaultCode (#213)
UINT
0…8116hex 0
In
Faulted state, FaultCode indicates the
fault that caused the transition to
Faulted. If not in Faulted state, FaultCode
indicates the fault that caused the last
transition to the Faulted state.
Fault codes are listed in appendix C
*14
Get
WarningCode (#214)
UINT
0…8116hex
0
In Warning state, WarningCode
indicates the warning that caused the
transition to Warning. If not in Warning
state, WarningCode indicates the
warning that caused the last transition
to the Warning state.
Warning codes are listed in appendix C