Instance attributes – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual
Page 36

Publication 825-UM002A-EN-P - December 2000
A-14
Instance Attributes
Attribute
ID
Access Rule
Name
Data Type
Value
1
Get/Set
only get is
supported for
monitoring
parameters
Parameter Value
See Data Type
and Data Size
Attributes
Value Retrieved from
825/CET4
2
Get
Link Path Size
USINT
06
3
Get
Link Path
Segment type/port
Segment address
BYTE
path data
dependent
Path to specific device
object attribute if
applicable
4
Get
Descriptor
WORD
Parameter Dependent:
0000000000ab0cd0
a-Monitoring Parameter
b-Read Only Parameter
c-Scaled Parameter
d-Enumerated String
5
Get
Data Type
USINT
Parameter Dependent
6
Get
Data Size
USINT
Parameter Dependent
7
Get
Parameter Name
SHORT_
STRING
Parameter Dependent
8
Get
Units String
SHORT_
STRING
Parameter Dependent
9
Get
Help String
SHORT_
STRING
Help String
10
Get
Minimum Value
data type
Parameter Dependent
11
Get
Maximum Value
data type
Parameter Dependent
12
Get
Default Value
data type
Parameter Dependent
13
Get
Scaling Multiplier
UINT
01
14
Get
Scaling Divisor
UINT
01
15
Get
Scaling Base
UINT
01
16
Get
Scaling Offset
INT
can be
negative
00
17
Get
Multiplier Link
UINT
0
18
Get
Divisor Link
UINT
0
19
Get
Base Link
UINT
0
20
Get
Offset Link
UINT
0
21
Get
Decimal Precision
USINT
Parameter Dependent