Instance attributes, continued – Rockwell Automation 825-MDN Smart Motor Manager DeviceNet Communication Card User Manual User Manual
Page 60

Publication 825-UM002A-EN-P - December 2000
A-38
Instance Attributes, Continued
Attribute
ID
Access
Rule
Name (param. #)
Data
Type
Min/Max
Units
Default
Description
109
Get/Set
as_prot_ (#28)
BOOL
0…1
1=ON
1
Asymmetry-protection, on/off
110
Get/Set
as_tr_le (#29)
USINT
5…80
%
35
Asymmetry, trip level
111
Get/Set
as_tr_ti (#30)
USINT
10…250
0.1 s
25
Asymmetry, trip delay (1.0…25.0 s)
112
Get/Set
as_alarm (#32)
BOOL
0…1
0=OFF
0
Asymmetry warning, on/off
113
Get/Set
as_al_le (#33)
USINT
5…80
%
20
Asymmetry, warning level
114
Get/Set
ol_prot_ (#35)
BOOL
0…1
1=ON
1
Overcurrent/locked rotor trip, on/off
115
Get/Set
ol_tr_le (#36)
USINT
10…60
times
0.1*FLC
24
Overcurrent/locked rotor, trip level
(1.0…6.0 times FLC)
116
Get/Set
ol_tr_ti (#37)
USINT
1…50
0.1 s
5
Overcurrent/locked rotor, trip delay
(0.1…5.0 s)
117
Get/Set
ol_alarm (#39)
BOOL
0…1
0=OFF
0
Overcurrent/locked rotor warning on/off
118
Get/Set
ol_al_le (#40)
USINT
10…60
times
0.1*FLC
20
Overcurrent/locked rotor warning level
(1.0…6.0 times FLC)
119
Get/Set
ef_prot_ (#42)
BOOL
0…1
1=ON
1
Earth-fault protection, on/off
120
Get/Set
efh_prot (#43)
BOOL
0…1
1=ON
1
Earth-fault prot., (Holmgreen) on/off
121
Get/Set
efh_tr_l (#44)
USINT
10…100
% Current 50
Earth fault (Holmgreen), trip level
122
Get/Set
efh_tr_t (#45)
USINT
1…50
0.1 s
5
Earth fault (Holmgreen), trip delay
(0.1…5.0 s)
123
Get/Set
efs_prot (#47)
BOOL
0…1
0=OFF
0
Earth-fault protection (core balance), on/
off
124
Get/Set
efs_tr_l (#48)
UINT
5…50000
0.005 A
1000
Earth-fault (core balance), trip level
125
Get/Set
efs_tr_t (#49)
USINT
1…50
0.1 sec
5
Earth-fault (core balance), trip delay
(0.1…5.0 s)
126
Get/Set
efs_al__ (#51)
BOOL
0…1
0=OFF
0
Earth-fault (core balance), warning on/off
127
Get/Set
efs_al_l (#52)
UINT
5…50000
0.005 A
500
Earth-fault (core balance), warning level
128
Get/Set
sc_prot_ (#54)
BOOL
0…1
0=OFF
0
Short circuit protection, on/off
129
Get/Set
sc_tr_le (#55)
USINT
40…120
times
0.1*FLC
100
Short circuit, trip level (4.0…12.0 times
FLC)
130
Get/Set
sc_tr_ti (#56)
USINT
2…99
10 ms
5
Short circuit, trip delay (20…990 ms)
131
Get/Set
ul_prot_ (#58)
BOOL
0…1
0=OFF
0
Underload protection, on/off
132
Get/Set
ul_tr_le (#59)
USINT
25…100
% FLC
75
Underload, trip level
133
Get/Set
ul_tr_ti (#60)
USINT
1…60
seconds
10
Underload, trip delay
134
Get/Set
ul_del_t (#62)
USINT
0…240
seconds
0
Underload trip, start delay
135
Get/Set
ul_alarm (#63)
BOOL
0…1
0=OFF
0
Underload warning, on/off