Troubleshooting
Chapter 3
Clear Alarms
Alarms are automatically cleared when the condition that caused the alarm is no
longer present.
Common Drive Symptoms
and Corrective Actions
Drive does not Start from Start or Run Inputs Wired to the Terminal
Block
Drive does not Start from HIM
Cause(s)
Indication
Corrective Action
Drive is Faulted
Flashing red status light
Clear fault.
• Press Stop
• Cycle power
• Set [Fault Clear] to 1 (see
)
• “Clear Faults” on the HIM Diagnostic
menu.
Incorrect input wiring. See pages Installation
Manual for wiring examples.
• 2 wire control requires Run, Run Forward,
Run Reverse or Jog input.
• 3 wire control requires Start and Stop inputs.
• Jumper from terminal 17 to 20 is required
when using the 24V DC internal supply.
None
Wire inputs correctly and/or install
jumper.
Incorrect digital input programming.
• Mutually exclusive choices have been made
(i.e., Jog and Jog Forward).
• 2 wire and 3 wire programming may be
conflicting.
• Exclusive functions (i.e, direction control)
may have multiple inputs configured.
• Stop is factory default and is not wired.
None
Program [Digital Inx Sel] for correct
inputs (see
Start or Run programming may be
missing.
Flashing yellow status light
and “DigIn CflctB”
indication on LCD HIM.
[Drive Status 2] shows type
2 alarm(s).
Program [Digital Inx Sel] to resolve
).
Remove multiple selections for the same
function.
Install stop button to apply a signal at
stop terminal.
Cause(s)
Indication
Corrective Action
Drive is programmed for 2 wire control. HIM
Start button is disabled for 2 wire control.
None
If 2 wire control is required, no action
needed.
If 3 wire control is required, program
[Digital Inx Sel] for correct inputs (see
).