Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual
Page 29

Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
29
Programming and Parameters
Chapter 2
SPEE
D C
O
MMAND
Pr
oc
es
s P
I
133 [PI Preload]
Sets the value used to preload the integral
component on start or enable.
Default:
Min/Max:
Units:
0.0 Hz
100%
–/+800.0%
0.1%
079
124
thru
138
134 [PI Status]
Status of the Process PI regulator.
1 = Condition True
0 = Condition False
Read Only
124
thru
138
135 [PI Ref Meter]
Present value of the PI reference signal.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
124
thru
138
136 [PI Fdback Meter]
Present value of the PI feedback signal.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
124
thru
138
137 [PI Error Meter]
Present value of the PI error.
Default:
Min/Max:
Units:
Read Only
–/+100.0%
0.1%
124
thru
138
138 [PI Output Meter]
Present value of the PI output.
Default:
Min/Max:
Units:
Read Only
–/+100.0 Hz
–/+100.0%
0.1 Hz
0.1%
124
thru
138
460 [PI Reference Hi]
Scales the upper value of [PI Reference Sel] of the
source.
Default:
Min/Max:
Units:
100.0%
–/+100.0%
0.1%
461 [PI Reference Lo]
Scales the lower value of [PI Reference Sel] of the
source.
Default:
Min/Max:
Units:
–100.0%
–/+100.0%
0.1%
462 [PI Feedback Hi]
Scales the upper value of [PI Feedback] of the
source.
Default:
Min/Max:
Units:
100.0%
–/+100.0%
0.1%
463 [PI Feedback Lo]
Scales the lower value of [PI Feedback] of the
source.
Default:
Min/Max:
Units:
0.0%
–/+100.0%
0.1%
464 [PI Output Gain]
Sets the gain factor for [PI Output Meter].
Note: Added for firmware revision 3.001.
Default:
Min/Max:
Units:
1.000
–/+8.000
0.001
138
Fil
e
Gr
oup
No
.
Parameter Name & Description
Values
Rela
ted
Name
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
Re
se
rv
ed
PI
In
Li
m
it
PI
R
es
et
PI
H
old
PI
E
na
ble
d
Default
x
x
x
x
x
x
x
x
x
x
x
x
0
0
0
0
Bit
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0