Troubleshooting
Chapter 3
Fault Subcodes
Fault Subcodes can be viewed in parameters 543, 545, 547, 549, 551, 553, 555,
and 557 [Fault
x Subcode]. Each of these parameters corresponds with
parameters 243, 245, 247, 249, 251, 253, 255, and 257 [Fault
x Code],
respectively. For example, if parameter 243 [Fault 1 Code] displays “5” and
parameter 543 [Fault 1 Subcode] displays “273”, an over voltage fault (F5) has
occurred in the power unit of the drive.
Table 3 - Precharge Active Fault (F1) Subcodes
Table 4 - Under Voltage Fault (F4) Subcodes
Table 5 - Over Voltage Fault (F5) Subcodes
Table 6 - Motor Stall Fault (F6) Subcode
Table 7 - Heatsink Over Temperature Fault (F8) Subcodes
IGBT OverTemp
9
UnderVoltage
4
IGBT Temp Hw
31
UserSetCflct
139
Input Phase
17
UserSet Timer
99
IntDB OvrHeat
148
VHz Neg Slope
26
InverterFault
14
Waking
149
Load Loss
15
Zero Divide
54
Name
No.
Fa
u
lt
Alarm
Name
No.
Fa
u
lt
Alarm
Subcode
Description
273
The precharge circuit in the power unit is active.
289
The precharge circuit in power unit 1 is active.
305
The precharge circuit in power unit 2 is active.
Subcode
Description
273
The DC Bus voltage in the power unit is too low while the drive is in a run state.
529
The DC Bus voltage in the power unit is too low while the drive is in a run state.
545
The DC Bus voltage in power unit 1 is too low while the drive is in a run state.
561
The DC Bus voltage in power unit 2 is too low while the drive is in a run state.
785
The DC Bus voltage in the power unit fell too low during a fast stop.
Subcode
Description
273
There is an over voltage in the power unit.
289
There is an over voltage in power unit 1.
276
There is an over voltage in power unit 2.
277
There is an over voltage in the power unit.
Subcode
Description
400
The motor is operating at high current and low frequency and is not accelerating.
Subcode
Description
272, 273
There is a heatsink over temperature in the power unit.
274
There is a heatsink over temperature on the Power board of the power unit.
275
There is a heatsink over temperature in the U phase of the power unit (typically frame 11 and 13 drives).
276
There is a heatsink over temperature in the V phase of the power unit (typically frame 11 and 13 drives).
277
There is a heatsink over temperature in the W phase of the power unit (typically frame 11 and 13 drives).
288, 289
There is a heatsink over temperature in power unit 1 (typically frame 12 and 14 drives).
290
There is a heatsink over temperature on the Power board of power unit 1 (typically frame 12 and 14 drives).
291
There is a heatsink over temperature in the U phase of power unit 1 (typically frame 12 and 14 drives).
292
There is a heatsink over temperature in the V phase of power unit 1 (typically frame 12 and 14 drives).