Selected Option Definitions – [Analog Outx Sel], [Digital Inx Sel], [Digital Outx Sel]
381
385
389
[Dig Out1 Level]
[Dig Out2 Level]
[Dig Out3 Level]
Sets the relay activation level for options 10…15
in [Digital Outx Sel]. Units are assumed to match
the above selection (i.e. “At Freq” = Hz, “At
Torque” = Amps).
Default:
Min/Max:
Units:
0.0
0.0
0.0
0.0/1500.0
0.1
380
384
388
382
386
390
[Dig Out1 OnTime]
[Dig Out2 OnTime]
[Dig Out3 OnTime]
Sets the “ON Delay” time for the digital outputs.
This is the time between the occurrence of a
condition and activation of the relay.
Default:
Min/Max:
Units:
0.00 Secs
0.00 Secs
0.00 Secs
0.00/163.00 Secs
0.01 Secs
380
384
388
383
387
391
[Dig Out1 OffTime]
[Dig Out2 OffTime]
[Dig Out3 OffTime]
Sets the “OFF Delay” time for the digital outputs.
This is the time between the disappearance of a
condition and de-activation of the relay.
Default:
Min/Max:
Units:
0.00 Secs
0.00 Secs
0.00 Secs
0.00/163.00 Secs
0.01 Secs
380
384
388
Fil
e
Gr
oup
No
.
Parameter Name & Description
Values
Rela
ted
Option
Description
Related
At Speed
Relay changes state when drive has reached commanded speed.
380 384 388
Excl Link
Links digital input to a digital output if the output is set to “Input 1…6
Link.” This does not need to be selected in the Vector option.
361
…
366
Input 1-6 Link
When Digital Output 1 is set to one of these (i.e. Input 3 Link) in
conjunction with Digital Input 3 set to “Excl Link,” the Digital Input 3
state (on/off) is echoed in the Digital Output 1.
380 384 388
MOP Dec
Decrements speed reference as long as input is closed.
361
…
366
MOP Inc
Increments speed reference as long as input is closed.
361
…
366
Param Cntl (A.O.)
Parameter controlled analog output allows PLC to control analog
outputs through data links. Set in [Anlgx Out Setpt], par. 377…378.
342 345
Param Cntl (D.O.)
Parameter controlled digital output allows PLC to control digital outputs
through data links. Set in [Dig Out Setpt], parameter 379.
380 384 388
PI Reference
Reference for PI block (see
342 345
Run Level
RunFwd Level
RunRev Level
Provides a run level input. A run level input does not require a transition
for enable or fault, but does require a transition for a stop.
361
…
366
Run w/Comm
Allows the Comms start bit to operate like a run with the run input on
the terminal block. Ownership rules apply.
361
…
366