Table 10, “over current fault, Table 11, “ground fault (f13), Table 12, “load loss fault (f15) – Rockwell Automation 20C PowerFlex 700H Drives Programming User Manual
Page 73: Table 13, “input phase fault
Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
73
Troubleshooting
Chapter 3
Table 10 - Over Current Fault (F12) Subcodes
Table 11 - Ground Fault (F13) Subcode
Table 12 - Load Loss Fault (F15) Subcode
Table 13 - Input Phase Fault (F17) Subcodes
9047
A supply voltage hardware problem has been detected on the 20C-DG1 option
board.
Replace the 20C-DG1 option board.
9303
A supply voltage hardware problem has been detected on the 20C-DG1 option
board.
Replace the 20C-DG1 option board.
9559
A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
Replace the 20C-DG1 option board.
If this fault occurs again, replace the Main Control board.
9815
A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
10071
A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
10327
A single hardware problem has been detected in the safe disable inputs on the
20C-DG1 option board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
10583
A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.
Replace the 20C-DG1 option board.
10839
A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.
Replace the 20C-DG1 option board.
11096
A single hardware problem has been detected in the thermistor input on the
20C-DG1 option board.
Replace the 20C-DG1 option board.
11351
A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
11607
A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
11863
A single hardware problem has been detected in the safe disable inputs or in the
thermistor input on the 20C-DG1 option board.
Replace the 20C-DG1 option board. If this fault occurs again, replace the Main Control
board.
12119
The 20C-DG1 option board has been mounted in an incompatible Main Control
board that is not equipped with the Safe Disable function.
Replace the Main Control board.
12376
Parameter expander board, slot B, Therm Trip is set to OFF even if the jumper X12 is not cut.
Subcode
Description
Action
Subcode
Description
272, 273
There is an over current in the power unit.
275
There is an over current in the U phase of the power unit (typically frame 11 and 13 drives).
276
There is an over current in the V phase of the power unit (typically frame 11 and 13 drives).
277
There is an over current in the W phase of the power unit (typically frame 11 and 13 drives).
288, 289
There is an over current in power unit 1 (typically frame 12 drives).
291
There is an over current in the U phase of power unit 1 (typically frame 14 drives).
292
There is an over current in the V phase of power unit 1 (typically frame 14 drives).
293
There is an over current in the W phase of power unit 1 (typically frame 14 drives).
304, 305
There is an over current in power unit 2 (typically frame 12 drives).
307
There is an over current in the U phase of power unit 2 (typically frame 14 drives).
308
There is an over current in the V phase of power unit 2 (typically frame 14 drives).
309
There is an over current in the W phase of power unit 2 (typically frame 14 drives).
Subcode
Description
273
There is a ground fault in the power unit.
Subcode
Description
400
The motor underload protection has tripped.
Subcode
Description
273
One input line phase in the power unit is missing.