26
Rockwell Automation Publication 20C-PM001F-EN-P - March 2012
Chapter 2
Programming and Parameters
SPEED C
O
MMAND
Speed Re
fe
re
nces
096 [TB Man Ref Sel]
Sets the manual speed reference source when a
digital input is configured for “Auto/Manual.”
Note: Options 18…20 were added for firmware
revision 5.002.
(1)
“Analog In 2” is not a valid selection if it was
selected for any of the following:
- [Trim In Select]
- [PI Feedback Sel]
- [PI Reference Sel]
- [Current Lmt Sel]
- [Sleep Wake Ref]
Default:
Options:
1
1
2
3…8
9
18
19
20
“Analog In 1”
“Analog In 1”
“Analog In 2”
(1)
“Reserved”
“MOP Level”
“DPI Port1”
“DPI Port2”
“DPI Port3”
097
098
097 [TB Man Ref Hi]
Scales the upper value of the [TB Man Ref Sel]
selection when the source is an analog input.
Default:
Min/Max:
Units:
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
079
096
098 [TB Man Ref Lo]
Scales the lower value of the [TB Man Ref Sel]
selection when the source is an analog input.
Default:
Min/Max:
Units:
0.0
–/+[Maximum Speed]
0.1 Hz
0.01 RPM
079
096
D
isc
re
te
S
pee
ds
100 [Jog Speed 1]
Sets the output frequency when Jog Speed 1 is
selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
079
101
102
103
104
105
106
107
[Preset Speed 1]
[Preset Speed 2]
[Preset Speed 3]
[Preset Speed 4]
[Preset Speed 5]
[Preset Speed 6]
[Preset Speed 7]
Provides an internal fixed speed command value.
In bipolar mode direction is commanded by the
sign of the reference.
Default:
Min/Max:
Units:
5.0 Hz/150 RPM
10.0 Hz/300 RPM
20.0 Hz/600 RPM
30.0 Hz/900 RPM
40.0 Hz/1200 RPM
50.0 Hz/1500 RPM
Based on Drive Rating
–/+[Maximum Speed]
0.1 Hz
1 RPM
079
090
093
108 [Jog Speed 2]
Sets the output frequency when Jog Speed 2 is
selected.
Default:
Min/Max:
Units:
10.0 Hz
300.0 RPM
–/+[Maximum Speed]
0.1 Hz
1 RPM
Speed T
rim
116 [Trim % Setpoint]
Adds or subtracts a percentage of the speed
reference or maximum speed. Dependent on the
setting of parameter 118 [Trim Out Select].
Note: Added for firmware revision 3.001.
Default:
Min/Max:
Units:
0.0%
–/+200%
0.1%
118
Fil
e
Gr
oup
No
.
Parameter Name & Description
Values
Rela
ted
32
32
32