I-1201 - sdo2 server parameter, I-1201, Communication manual 8400 motec canopen – Lenze E84DGFCC User Manual
Page 97: Implemented canopen objects

EDS84DMOTCAN EN 3.0 - 11/2011
L
97
Communication manual 8400 motec CANopen
Implemented CANopen objects
I-1201 - SDO2 server parameter
Setting of the identifiers for SDO server channel 2.
The server SDO parameter is only valid if bit 31 is set to "0" for both transmission
directions (subindex 1 and 2).
In the Lenze setting, SDO server channel 2 is deactivated (bit 31 = "1").
The identifier may only be changed when the SDO is invalid (bit 31 = "1").
[13-6] Data telegram assignment
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1201
Name:
SDO2 server parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
3
- (read access only)
ro
U8
1: COB-ID client -> server (rx)
0x80000000
0
4294967295 rw
U32
2: COB-ID server -> client (tx)
0x80000000
0
4294967295 rw
U32
Subindex
Meaning
1
Specification of the receive identifier
2
Specification of the transmit identifier
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31
Bit 30
Bit 29 ... bit 11
Bit 10 ... bit 0
0/1
0
Extended identifier*
11-bit identifier
* The extended identifier is not supported - bit 11 ... bit 29 must be set to "0".
Bit
Setting
Bit 31
0 SDO is valid.
1 SDO is invalid.