Consider the use of repeaters, Communication manual 8400 motec canopen – Lenze E84DGFCC User Manual
Page 28

Communication manual 8400 motec CANopen
Installation
Electrical installation
28
L
EDS84DMOTCAN EN 3.0 - 11/2011
Consider the use of repeaters
Conclusion:
A cable length of 450 m is not possible without installing a repeater.
After 360 m (step 2), a repeater must be installed.
Result:
The Lenze repeater, type 2176 (cable reduction: 30 m), is used
Calculation of the max. cable length:
– First segment: 360 m
– Second segment: 360 m (according to the table
)
minus 30 m (cable reduction when a repeater is used)
Max. possible cable length with one repeater: 690 m
– Now the required cable length is possible.
Note!
The use of an additional repeater is recommended as:
• Service interface
– Advantage: Trouble-free connecting during ongoing bus operation is
possible.
• Calibration interface
– Advantage: Calibration/programming units remain electrically isolated.
Given
• Baud rate:
125 kbps
• Cable cross-section:
0.5 mm
2
• Number of nodes:
28
• Cable length:
450 m
Steps
Cable length
See
1
Total cable length at 125 kbps:
600 m
Table
2
Segment cable length for 28 nodes and a
cable cross-section of 0.5 mm
2
:
360 m
Table
3
Comparison: The value determined in
step 2 is smaller than the required cable