I-1801 - TPDO2 communication parameter
Communication parameters for sending process data via TPDO2
For data telegram assignment and description of subindexes, see object
How to change the identifier:
1. Deactivate identifier (set bit 31 to "1").
2. Change identifier.
3. Activate identifier (set bit 31 to "0").
Index:
I-1801
Name:
TPDO2 communication parameter
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
5
- (read access only)
ro
U8
1: COB-ID used by TPDO
0x280 + node ID
0
4294967295 rw
U32
2: Transmission type
254
0
255 rw
U8
3: Inhibit time
0 ms
0
0.1 ms
65535 rw
U16
4: Reserved
-
- (reserved, read or write access results in error
message 0x06090011)
rw
U8
5: Event timer
0 ms
0
ms
65535 rw
U16
Subindex
Meaning
Code
0
The value 5 is permanently set.
• Max. 5 subindexesare supported.
-
1
TPDO2 identifier
• According to the "Predefined Connection Set", the
basic setting is: identifier = 0x280 + node ID
2
TPDO transmission type according to DS301 V4.02
3
Minimum time between sending two identical TPDOs
(see DS301 V4.02).
-
5
Cycle time for PDO transmission with transmission type
"254".