I-1016 - consumer heartbeat time, I-1017 - producer heartbeat time, I-1017 – Lenze E84DGFCC User Manual
Page 95: The parameterised time is rounded, Object, I-1016, Communication manual 8400 motec canopen, Implemented canopen objects
![background image](/manuals/565821/95/background.png)
EDS84DMOTCAN EN 3.0 - 11/2011
L
95
Communication manual 8400 motec CANopen
Implemented CANopen objects
I-1016 - Consumer heartbeat time
Monitoring time for the nodes to be monitored via heartbeat.
The parameterised time is rounded down to an integer multiple of 5 ms and must have a
greater value than the heartbeat producer time of the node to be monitored.
[13-4] Data telegram assignment
I-1017 - Producer heartbeat time
Time interval for the transmission of the heartbeat telegram to the consumer(s).
The parameterised time is rounded down to an integer multiple of 5 ms.
The heartbeat telegram is sent automatically as soon as a time > 0 ms is set. In this case
the monitoring function "Node Guarding" is deactivated.
This object relates to code
Index:
I-1016
Name:
Consumer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Highest subindex supported
1
- (read access only)
ro
U16
1 ... n: Consumer heartbeat time
0
0
65535 rw
U16
Subindex
Meaning
Lenze code
0
Number of nodes to be monitored
1 ... n
Node ID and heartbeat time of the node to be monitored Node ID:
Heartbeat time:
8th byte
7th byte
6th byte
5th byte
Data 4
Data 3
Data 2
Data 1
Bit 31 ... bit 24
Bit 23 ... bit 16
Bit 15 ... bit 0
0
Reserved
Node ID
Heartbeat time
in [ms]
Index:
I-1017
Name:
Producer heartbeat time
Subindex
Default setting
Setting range (min. value | unit | max. value)
Access
Data type
0: Producer heartbeat time
0
0
ms
65535 rw
U16